TAH Flashcards
State auto open for TAH louvers and dampers
at 88F louvers and dampers open for natural cirulation
State auto start for TAH roof fans
at 95F roof fans start if its damper and louver is full open
State how TAH responds to fire conditions
In case of a fire, if TB zone temperature >145°F (HB >115°F), the associated louver and roof damper auto-opens and the power roof ventilator auto-starts for heat/smoke removal.
State how TAH responds to cold outside temperatures
If outside air temperature <35°F, TB/HB louvers & dampers auto-close (which automatically trips the power roof ventilators),
Discuss how the Lube Oil storage building ventilation works
An outside supply fan (1000 scfm) provides ventilation and prevents the accumulation of explosive gases.
A heating coil within the supply duct maintains temperature >55°F.
Air is exhausted through fire dampers, which have 165ºF fusible links.
State how Lube Oil Storage Building heating is prevented from freezing
On low system demand there is a bypass orifice which keeps the piping warm