TAH Flashcards

1
Q

State auto open for TAH louvers and dampers

A

at 88F louvers and dampers open for natural cirulation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State auto start for TAH roof fans

A

at 95F roof fans start if its damper and louver is full open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

State how TAH responds to fire conditions

A

In case of a fire, if TB zone temperature >145°F (HB >115°F), the associated louver and roof damper auto-opens and the power roof ventilator auto-starts for heat/smoke removal.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State how TAH responds to cold outside temperatures

A

If outside air temperature <35°F, TB/HB louvers & dampers auto-close (which automatically trips the power roof ventilators),

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Discuss how the Lube Oil storage building ventilation works

A

An outside supply fan (1000 scfm) provides ventilation and prevents the accumulation of explosive gases.
A heating coil within the supply duct maintains temperature >55°F.
Air is exhausted through fire dampers, which have 165ºF fusible links.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

State how Lube Oil Storage Building heating is prevented from freezing

A

On low system demand there is a bypass orifice which keeps the piping warm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly