Integrated Safeguards Flashcards

1
Q

State Containment DBA

A

Double ended break of RCP piping
One CBS train Fails to start
One EDG fails to start
52# max calculated containment pressure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

State other action of P-11

A

Blocking P-11 will block MS low steam line pressure (585#) SI
AND
Enables Steam Line Pressure rate hi MSI (100# for 50 sec)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

State what a “Dual Function” valve means

A

Dual Function valves are valves that comply with more than 1 T.S. and compliance with one will mean non-compliance with the other T.S.
See OPMM for guidance

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

List the Five Major categories of ESF

A
Containment systems
ECCS
Habitability systems
Fission product removal and control systems
EFW
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

List the 4 Subsystems that are part of the Containment system

A

Primary containment and enclosure structures
Containment heat removal systems
Containment isolation systems
Combustible gas control systems

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

State plant response to SI

A
RX trip
ECCS actuation
EFW
CBA goes to filter recir mode
EDG start
Phase A isolation
CVI
FWI
Turbine trip
MFP trip
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

State plant response to Phase A

A
Isolation of non containment
CVI
Electrical penetration sump pump trips
Initiates CC to RHR HX
EAH to emergency mode
starts EAH fans
Isolates IA to Containment
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

State plant response to Phase B

A

Isolates CC to containment (not thermal barrier)
Opens CC to CBS HX
Trips CRDM cooling fans
Starts CAH-FN-3A/B in recirculation mode

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

State plant response to CVI

A
Trips Make up fans (27 A/B)
Closes Make up fans dampers (53 A/B)
Opens DP-27A/B
which starts FN-16A/B
Exhaust FN-15 Trips
Exhaust dampers (28/1058) close
How well did you know this?
1
Not at all
2
3
4
5
Perfectly