State the potentially contaminated areas of the PAB that PAH serves
Charging Pump Rooms Demin Alley VCT area Sample Heat Exchanger Room Fume hood LTDN Hx and Filter Cells Pipe Tunnel Degasifier area
State flow path for potentially contaminated areas
PAB Supply fans potentially contaminated areas return ducting PAH Cleanup Filter (F-16) Filter Exhaust fans Plant Vent Stack
State PCCW air cooling alignment on LOP
Uses Safety Related A & B Train Fans and Dampers
PAH-FN-42-A / DP-43-A/DP-357
PAH-FN-42-B / DP-43-B/DP-358
State flow path for Safety Related PCCW air cooling
- Outside air through Intake Louver to PAB Service Water Slot air Plenum
- A & B train PCCW Area Auxiliary Supply Dampers/Fans (DP-43-A/ B and FN-42-A / B)
- into PCCW Pump Area
- to Outlet Dampers (DP-357 / 358)
- back to Outside
State how PCCW area cooling responds on high temperatures
If PCCW Pump area temperature reaches High I setpoint (105F):
- Lead train (A) inlet damper and outlet damper open
- Lead train (A) supply fan starts
If PCCW Pump area temperature reaches High II setpoint (110F):
- Lag train (B) inlet damper and outlet damper open
- Lag train (B) supply fan starts
State how PAH/EAH respond on T-signal
PAH supply/exhaust dampers (35A/B and 36A/B) auto close
Fan 180 B starts due to low differential pressure
EAN-FN-180B or 180A provides CS pump room exhaust ventilation To maintain cooling for Charging Pump Motors
180B is preferred fan
180A is a backup and starts after 150 second time delay if 180B fails to start
No affect on previously running FN-5A/B or FN-31A/B
Emergency filter unit fans EAH-FN-4A & 4B start
FN-4A and 4B develop a negative pressure in all enclosure areas
FN-4A/B exhaust flow routed to Plant Vent Stack
State how PAH Dampers respond on LOP
PAH dampers 35A/36A close on loss of power
State how PAH (EAH) Fans responds on LOP
EAH-FN-5A/B previously running fan is restarted by Sequencer
FN-31A or 31-B The train associated exhaust fan aligned for Auto will restart after the previously FN-5A or B restarts (not started by sequencer)
Describe how EAH-FN-180 respond to LOP
FN-180 B will auto start when the D/G breaker closes and the low d/p switch actuates
FN-180 A will auto start 150 seconds later if:
180 B fails to start (Low d/p ) &
Sequencer at step 9