Waste Gas (WDS) Flashcards

1
Q

What does the WGC inlet isolation valve do?

A

Prevents short-circuiting gas thru the standby WGC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What does the WGC Moisture Sep Unloader valve do?

A

Prevents compressor from starting under load

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What does the WGC Moisture Sep Gas Recycle Valve do?

A

Controls vent header pressure by opening to recycle waste gas from moisture separator back to vent header

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the interlock associated with the GDT Inlets?

A

Only 1 can be open at a time

“Break before make”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When will the I/S GDT swap to the Standby GDT?

A
  • Hi-Hi oxygen (from AOM)
  • In Service GDT gets to 100#

only swaps if a standby tank is selected

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

At what constant pressure does RRV-305 (Waste Gas Release pressure Ctrl Valve) maintain the inlet pressure to RRV-306?

A

5 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does RRV-306 (Waste Gas Release Flow Ctrl valve) do?

A

Manually positioned to control release FLOW rate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What will trip RRV-306 (Waste Gas Release Flow Ctrl valve) closed?

A
  • Loss of both U1 AX Fans
  • High Rad on U1 or U2 Vent Stack Rad Monitors (VRS-1500/2500)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What interlock does RRV-306 have to open?

A
  • At least 1 AX must be running**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Where does the AOM sample the waste gas header

A

Discharge of the moisture separator on the WGC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the normal waste gas vent header pressure?

A

Between 1.3 - 2.0 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly