EDG AUX Flashcards
When do the EDG Supply and Exhaust fans stop?
- Stop 30 min after EDG shutdown
- 70°F Room Temp
- On acutation of CO2
How often does the gear lube oil ctrl valve open while the EDG is in stby?
Solenoid opens every 4 hours for 2 min
When do the gear lube oil ctrl valves close after the EDG is shutdown?
8 min after an EDG is shutdown/tripped
When is the field flash disabled?
80% speed during a fast start
When does the supply fan for the EDG Auto start?
- 20 Sec after an EDG start
- 95°F Room Temp
When does the exhaust fan for the EDG Auto start?
- EDG start
- 95°F Room Temp
What are the designed temp bases for the EDG room?
< 104°F in standby
< 130°F running
When does the Stby EDG JW Pump auto start?
Low # (16 psig)
10 sec time delay
What temp does the EDG Aux Jacket Water Heater maintain the EDG Jacket Water at?
145°F
Unit 1 is at 100% power. A relief valve has failed open on 1AB Emergency Diesel Generator Starting Air Receiver #1. The associated starting air compressor has tripped off. What is the response of 1AB Emergency DieselGenerator if a start signal occurs before any operator action? The EDG will …
start in the normal time from #2 Starting Air Receiver but only one starting air valve will supply all of the cylinders with starting air pressure.
Upon a loss of control air, EDG air aftercooler regulating valves fail to what position?
Fails to allow full flow through the EDG air aftercooler
EDG Valve Gear Lube Oil valves fail how on a loss of Ctrl Pwr?
Open
What is the cooling supply to the EDG Woodward Electronic Governor?
Jacket Water