EDGS Flashcards

1
Q

What are the EDG Trips available Without DC Power?

A
  • Mechanical Overspeed (112% of 514 RPMs)
  • Worthington/Manual Fuel Valve (MFV)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the only EDG TRIPS available after the EDG Auto Starts on an SI or Load Shed? (With 250 VDC Available)

A
  • Gen Phase Differential
  • Electronic Overspeed (110%)
  • Manual Push Button
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the EDG Starts?

A
  • CR Control Switch
  • Local Push Button
  • Load Shed (loads to bus)
  • SI (does not load to bus)
  • Worthington/Manual Starting Air Valve (allows start during loss of 250VDC control power)
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How do the starting air valves fail on a loss of 100# ctrl air?

A

Fail as is

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What happens on a failure of the electronic governor?

A

EDG will speed up until Mechanical Governor takes over

set point for mech governor is 60.8-61 hz

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where does the field flash come from on a fast speed start?

A

From the 1kV inverter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where does the field flash come from on a slow speed start?

A

From residual magnetism

From 1kV loads IF button is used to flash the field

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What are the 1KV inverter Loads?

A
  • Field Flash (Fast Start) (Slow Start if button is pushed)
  • Bearing Temp Monitor (SG-40)
  • Speed Transmitters
  • Local/Remote Control Transfer Relays
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How long does the Throttle Control Cylinder (TCC) extend for on a EDG Trip and why?

A

TCC will extend for 2 minutes on trip to prevent re-start of EDG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Will a EDG start with a loss of 100 psi Ctrl Air?

A

NO!
TCC extends on loss of 100 psi control air

it will trip if running, also

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What causes Load Shed to be disabled?

A

EDG output breaker control switch is in close or lockout

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When do run relays energize to allow power to bus?

A

At 95% running speed

start aux equip, input to load cons and provide interlocks/permissives

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

If an emergency start signal initiates at any time during the slow start, what will happen?

A

The slow start circuit automatically drops out and an emergency start takes place (Fast Speed)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Are the EDG trip relays energize or de-energize to trip?

A

Energize to Trip

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Are the EDG start relays energize or de-energize to run?

A

De-Energize to run
(1 per bus – want to run if lost power)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Why is the EDG considered Inop during a surveillance?

A

Because the Load Shed signal is deactivated

17
Q

How is ctrl air designed to fail on a loss of 250V DC?

A

so that control air will be available to the TCC

18
Q

What is the auto trip available with a loss of 250V DC?

A

Mechanical Overspeed

(112% of 514 rpms)

19
Q

What supplies power to the EDG 1Kv inverter

A

250v DC Charger/Battery (Train Specific)

20
Q

What loads sequence on during a load shed WITH a SI?

A

CCP
SI pump
RHR pump
CCW pump
ESW pump
MDAFW pump
CTS pump (Starts when Phase B active)
NESW pump (Starts/Then Trips if CTS/Phase B active)

21
Q

Will the loss of HVAC make the EDG INOPERABLE?

A

YES

22
Q

What ventilation is required by TS LCO 3.8.1 for an EDG to be OPERABLE?

A

Supply Fan, Exhaust Fan and Cabinet Fan

23
Q

When is the field flash disabled during a fast speed start?

A

80% Speed

24
Q

What happens to an EDG in standby if a CO2 discharge occurs in the EDG CD room?

A

The CO2 actuation signal trips the 87X relay. It must be reset or the EDG will not start when needed