UNIT 7: Ex i Flashcards
1.
Which one of the following locations may· Ex ib equipment be used?
EPL Gc (Cat 3G) only
EPL’s Gb, Gc (Cat’s 2G,Cat 3G)
EPL Ga (Cat 1 G)
EPL’s Ga, Gb, Gc (Cat’s 1G, 2G ,3G);
EPL’s Gb, Gc (Cat 2G, Cat 3G)
2.
The comparison between Ex nL and Ex ic is correctly stated by which one of the following statements?
Both may be used in zones 0, 1, and 2
Both may be used in zone 2 only
Ex nL may be used in zones 0, 1 and 2 and Ex nL in zone 2 only
Ex ic can be installed in zones 0, 1 , 2 Ex nL in zone 2 only.
Both may be used in zone 2 only
3.
The maximum resistance of the cables connecting a zener barrier earth bar and the main earth should not exceed?
1 ohm
10 ohms
1M ohms
100 ohms
1 ohm
4.
Which one of the following colours is recommended for the identification of IS cables?
White
Yellow
Light blue
Red
Light Blue
5.
The minimum cross-sectional area of a single IS earth conductor is?
- 0 mm2
- 0 mm2
- 5 mm2
- 0 mm2
4.0 mm2
Note: two separate earth conductors with minimum cross-sectional area of 1.5mm2 was listed in previous editions and notes, however two x 1.5mm2 copper conductors is not listed in current editions And instead only list Minimum size as 4mm2 copper earth conductor. ASET training Center still list 2 x 1.5mm2 copper conductors as acceptable (as few when Course done 19-Nov20)
With maximum impedance of 1.0 ohms. The provision of two earth conductors
Should be considered to facilitate testing.
6.
The equipment in the hazardous area which may be connected to the output of a zener barrier is which one of the following?
Equipment specified in the documentation and simple apparatus;
The apparatus specified in the documentation only
Any equipment
Any IS certified equipment and simple apparatus
The apparatus specified in the documentation only.
7.
Which one of the following statements indicates the correct requirements for an installation comprising both IS and non-IS circuits?
IS and non-IS cables may be installed side-by-side
IS and non-IS cables must be run on sparate cable trays
Non-IS cables must always be screened, armoured or metal sheathed
Either the IS or non-IS cables need only be armoured, screened or metal
sheathed.
Either the IS or non-IS cables need only be armoured, screened or metal sheathed.
Methods of Segregating IS and Non-IS circuits.
a. Adequate separation between IS circuits and non-IS circuits. Example: IS and Non-IS cables on different cable trays.
b. Positioning of the IS circuit cables such as to guard against the risk of mechanical damage. Example: IS and Non-IS cables on the same cable tray but separated by either an insulated or earthed partition.
c. The use of armoured, metal sheathed, or screened cables for either the IS or Non-IS cables, then separation with this method is unnecessary. Example: IS and Non-IS cables in the same tray but segregation is afforded by one of the cable types being armoured, screened or metal sheathed.
8.
The minimum clearance between different adjacent IS circuits is?
50mm
3mm
5mm
6mm
6mm
Minimum clearance between IS circuit, bare-conductor, and earth is 3mm.
Minimum clearance between different IS circuits, bare-conductors is 6mm.
Minimum clearance between IS and Non-IS circuits is 50mm.
9.
The maximum permitted supply voltage (Um) at the non-IS terminals of an IS
installation is?
250V
28V
As specified in the documentation
115V.
As specified in the documentation
10.
An appropriate workshop test for a faulty zener barrier with a possible blown fuse would be?
Disconnect output and measure voltage
Check the incoming supply voltage after suitable safety precautions have been applied
Place barrier in a test rack and measure the current
Disconnect and measure the resistance between the barrier input and output terminals.
Disconnect and measure the resistance between the barrier input and output terminals.
11.
From the following statements, which one has equipment that does not require a dedicated IS earth?
Barrier used in circuit installed in group IIC gases
Zener barrier with output connected in hazardous area
24V zener barrier
Galvanic isolation barrier.
Galvanic isolation barrier.
12.
What does the marking, [Ex ib] IIC, on an item of IS equipment indicate?
It is intrinsically safe and for use with IIC gases
It is intrinsically safe and can be installed anywhere
It may only be installed in a non-hazardous area
It is equipment associated with IS circuits.
It is equipment associated with IS circuits.
13.
The minimum clearance between IS terminals and earth is?
30mm
50mm
3mm
6mm
3mm
Minimum clearance between IS circuit, bare-conductor, and earth is 3mm.
Minimum clearance between different IS circuits, bare-conductors is 6mm.
Minimum clearance between IS and Non-IS circuits is 50mm.
14.
The screen of a cable in an IS circuit must be connected to,
The main earth conductor;
The point indicated on the loop (hook up) diagram;
Earth at both ends
Earth at one end only.
The point indicated on the loop (hook up) diagram;
15.
Equipment marked Ex d [ia] indicates that?
The flameproof enclosure is deemed ‘simple apparatus’ in an ‘ia’ circuit
The flameproof enclosure contains associated IS equipment
The components inside are all intrinsically safe
Electrical items other than IS items are inside.
The flameproof enclosure contains associated IS equipment
16.
IS cables with screens will have sheathing capable of withstanding which one of the following test voltages?
500Vac and 750Vdc
500Vac or 750Vdc
1000V
Double the working voltage. The
500Vac or 750Vdc
IR test voltage is
Twice I.S. Circuit Voltage or
500 vac or
750 vdc
On a sample of circuit periodically.
IR testing of IS circuits
IR test of IS circuits is required on Sample Inspections only
(IEC 60079-17 Table 2, B.9)
The IR test instrument for testing IS circuits must be specifically approved for use on IS circuits.
Test voltage 500vac or 750vdc.
The conductors of IS cables are required to be insulated with elastomeric or thermoplastic insulation with a minimum thickness of 0.3mm. The cables must be capable of withstanding a 500vac or 750vdc test voltage between …
conductors and earth
conductors and screens, and
screen to earth.
17.
Power supply modules for an Ex ia circuit are to be located in an area requiring EPL Gc (Cat 3G) equipment. In which one of the following enclosures may the modules be fitted?
Ex e/i
Ex p
Ex e
Ex n.
Ex p