UNIT 4 & 5: Ex e Ex n Flashcards
1.
The minimum IP rating for Ex e equipment is?
IP64
IP6X
IP44
IP54
IP54
2.
Which one of the following descriptions represents equipment marked Exe?
Intrinsically safe
Increased safety
Flameproof
Enhanced safety.
Increased safety
3.
Which one of the following locations may Ex n equipment be installed?
EPL Gb (Cat 2G) locations only
EPL Gc (Cat 3G) locations only
EPL Ga (Cat 1G) locations
EPL’s Gb, Gc (Cats 2G, 3G) locations.
EPL Gc (Cat 3G) locations only
4.
Four variations of Ex n equipment are available, which are?
Na, Ne, NL, Nr
nA, nB, nC, nD
px, py, pz
nA, nC, nL, nR.
nA, nC, nL, nR.
5.
Installed in 2009, an Ex d motor has an Ex e terminal box. Which one of the following gland options may be used on a SWA cable?
Uncertified E1W
Ex i
Ex d
Ex d or Exe
Ex d or Exe
6.
A steel Ex e enclosure has a threaded entry 10mm in length. Which one of the following options achieves the minimum installation requirement when fitting an Ex e cable gland?
Fit gland
Fit gland, external IP washer and internal serrated washer
Fit gland, external IP washer and internal lock nut
Fit gland, earth tag, serrated washer and internal lock nut.
Fit gland
7.
For Ex e equipment installed in 2005, which one of the following glands is not acceptable?
Ex e certified
Uncertified
Ex d certified
Uncertified plastic.
Uncertified plastic.
8.
The te time of an Ex e motor indicates?
The disconnection time limit when stalled after starting from cold
The disconnection time limit when stalled after starting from hot
The run-up time to full speed
The minimum time interval between re-starts.
The disconnection time limit when stalled after starting from hot
9.
The requirements for cable glands entering Ex n equipment after 2007 are?
Ex d barrier gland
Ex e certified gland
Certified as meeting the requirements of IEC60079-0
Ex d certified gland.
Certified as meeting the requirements of IEC60079-0
10.
An Ex de motor, with an Ex e terminal box, was installed in 2005. Which one of the following cable glands .achieves the minimum installation requirements:
An E1W. Exe gland
An E1WF Ex d gland
An uncertified gland which meets the IP and impact requirements
An Ex d gland
An uncertified gland which meets the IP and impact requirements
11.
A steel Ex e enclosure has clearance entries. What is the minimum requirement
for installing an SWA cable :
Fit gland, internal IP washer, serrated washer and locknut
Fit gland, earth tag, serrated washer and internal locknut
Fit gland, external IP washer, internal serrated washer and locknut
Fit gland, external IP washer and internal locknut
Fit gland, external IP washer, internal serrated washer and locknut
12.
Which one of the following restrictions apply to Ex e and Ex n light fittings?
Lamps using non-conducting end-caps or pins with a conductive coating unless tested with the equipment
Lamps using conducting end-caps or pins are prohibited
Lamps with screwed connections are prohibited
Fluorescent lamps must be bi-pin.
Lamps using non-conducting end-caps or pins with a conductive coating unless tested with the equipment
13.
An increased safety enclosure is marked Ex e II T6. The absence of a letter after ‘II’ indicates the enclosure may be used in: Group IIC gases only
iGroup IIA gases only
All gas groups
iv In combustible dusts only.
All gas groups
14.
The purpose of seals at the joints of Exe enclosures is to:
prevent the ingress of dust and moisture
prevent the ingress of flammable gases I vapour
insulate the parts from one another
contain an internal explosion
prevent the ingress of dust and moisture
15.
A plastic Ex e enclosure has clearance entries and no internal continuity plate.
Which one of the following arrangements achieves the minimum requirements
when installing an Ex e cable gland
Fit gland and external IP washer
Fit gland, earth tag
internal locknut and external shroud
Fit gland, external IP washer and internal locknut
Fit gland, earth tag, external IP washer and internal locknut.
Fit gland, earth tag, external IP washer and internal locknut.