COMPEX Ex p Inspection Flashcards
TABLE 3 Ex p
A.1
EQUIPMENT IS APPROPRIATE TO THE EPL / ZONE REQUIREMENTS OF THE LOCATION
DETAILED
CLOSE
VISUAL
TABLE 3 Ex p
A.2
EQUIPMENT GROUP IS CORRECT
DETAILED
CLOSE
TABLE 3 Ex p
A.3
EQUIPMENT TEMPERATURE CLASS IS SURFACE TEMPERATURE IS CORRECT
DETAILED
CLOSE
TABLE 3 Ex p
A.4
EQUIPMENT CIRCUIT IDENTIFICATION IS CORRECT
DETAILED
TABLE 3 Ex p
A.5
EQUIPMENT CIRCUIT IDENTIFICATION IS AVAILABLE
DETAILED
CLOSE
VISUAL
TABLE 3 Ex p
A.8
ENCLOSURE, GLASS PARTS AND GLASS TO METAL SEALING GASKETS AND / OR COMPOUNDS ARE SATISFACTORY.
DETAILED
CLOSE
VISUAL
TABLE 3 Ex p
A.7
THERE ARE NO UNAUTHORISED MODIFICATIONS
DETAILED
TABLE 3 Ex p
A.8
THERE IS NO EVIDENCE OF UNAUTHORISED MODIFICATIONS
CLOSE
VISUAL
TABLE 3 Ex p
A.9
LAMP RATING, TYPE AND POSITION ARE CORRECT
DETAILED
TABLE 3 Ex p
B.1
TYPE OF CABLE IS APPROPRIATE
DETAILED
TABLE 3 Ex p
B.2
THERE IS NO OBVIOUS SIGNS OF DAMAGE TO CABLES.
DETAILED
TABLE 3 Ex p
B.3
EARTHING CONNECTIONS, INCLUDING ANY SUPPLEMENTARY EARTHING BONDING CONNECTIONS ARE SATISFACTORY (CONNECTIONS ARE CLEAN AND TIGHT AND CONDUCTORS ARE OF SUFFICIENT CROSS-SECTION) - PHYSICAL CHECK
DETAILED
TABLE 3 Ex p
B.3
EARTHING CONNECTIONS, INCLUDING ANY SUPPLEMENTARY EARTHING BONDING CONNECTIONS ARE SATISFACTORY (CONNECTIONS ARE CLEAN AND TIGHT AND CONDUCTORS ARE OF SUFFICIENT CROSS-SECTION) - VISUAL CHECK
CLOSE
VISUAL
TABLE 3 Ex p
B.4
FAULT LOOP IMPEDANCE (TN SYSTEMS) OR EARTHING RESISTANCE (IT SYSTEMS) IS SATISFACTORY.
DETAILED
TABLE 3 Ex p
B.5
AUTOMATIC ELECTRICAL PROTECTIVE DEVICES OPERATE WITHIN PERMITTED LIMITS.
DETAILED