COMPEX Ex d Inspection Flashcards

1
Q

TABLE 1 Ex d

A.1
EQUIPMENT IS APPROPRIATE TO THE EPL/ZONE REQUIREMENTS OF THE LOCATION.

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

TABLE 1 Ex d

A.2
EQUIPMENT GROUP IS CORRECT

A

DETAILED
CLOSE

Equipment Groups
Group Category Level of protection
Group I M1 Very High
Group I M2 High

Group II CAT 1 Very High
Group II CAT 2 High
Group II CAT 3 Normal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

TABLE 1 Ex d

A.3
EQUIPMENT TEMPERATURE CLASS IS CORRECT (GAS ONLY)

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

TABLE 1 Ex d

A.5
DEGREE OF PROTECTION (IP) OF EQUIPMENT IS APPROPRIATE FOR THE LEVEL OF PROTECTION/GROUP CONDUCTIVITY

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

TABLE 1 Ex d

A.6
EQUIPMENT CIRCUIT IDENTIFICATION IS CORRECT.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

TABLE 1 Ex d

A.7
EQUIPMENT CIRCUIT IDENTIFICATION IS AVAILABLE.

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

TABLE 1 Ex d

A.8
ENCLOSURE, GLASS PARTS AND GLASS TO METAL SEALING GASKETS AND / OR COMPOUNDS ARE SATISFACTORY.

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

TABLE 1 Ex d

A.9
THERE IS NO DAMAGE OR UNAUTHORISED MODIFICATIONS

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

TABLE 1 Ex d

A.10
THERE IS NO EVIDENCE OF UNAUTHORISED MODIFICATIONS

A

CLOSE

VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

TABLE 1 Ex d

A.11
BOLTS, CABLE ENTRY DEVICES (DIRECT AND INDIRECT) AND BLANKING ELEMENTS ARE OF THE CORRECT TYPE ARE COMPLETE AND TIGHT.
PHYSICAL CHECK

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

TABLE 1 Ex d

A.11
BOLTS, CABLE ENTRY DEVICES (DIRECT AND INDIRECT) AND BLANKING ELEMENTS ARE OF THE CORRECT TYPE ARE COMPLETE AND TIGHT.

A

VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

TABLE 1 Ex d

A.12
THREADED COVERS ON ENCLOSURES ARE OF THE CORRECT TYPE, ARE TIGHT AND SECURED.
PHYSICAL CHECK

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

TABLE 1 Ex d

A.12
THREADED COVERS ON ENCLOSURES ARE OF THE CORRECT TYPE, ARE TIGHT AND SECURED.

A

VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

TABLE 1 Ex d

A.13
JOINT FACES ARE CLEAN AND UNDAMAGED AND GASKETS, IF ANY, ARE SATISFACTORY.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

TABLE 1 Ex d

A.14
CONDITION OF ENCLOSURE GASKETS IS SATISFACTORY.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

TABLE 1 Ex d

A.15
THERE IS NO EVIDENCE OR INGRESS OF WATER OR DUST IN THE ENCLOSURE IN ACCORDANCE WITH THE IP RATING.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

TABLE 1 Ex d

A.16
DIMENSIONS OF FLANGE JOINT GAPS ARE WITHIN MAXIMUM VALUES PERMITTED

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

TABLE 1 Ex d

A.25
BREATHING AND DRAINING DEVICES ARE SATISFACTORY.

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

TABLE 1 Ex d

A.27
HIGH INTENSITY DISCHARGE LAMPS ARE NOT INDICATING END OF LIFE EFFECTS

A

DETAILS
CLOSE
VISUAL

20
Q

TABLE 1 Ex d

A.28
LAMP TYPE, RATING, PIN CONFIGURATION AND POSITION ARE CORRECT

21
Q

TABLE 1 Ex d

A.29
MOTOR FANS HAVE SUFFICIENT CLEARANCE TO ENCLOSURE AND / OR COVERS, COOLING SYSTEMS ARE UNDAMAGED, MOTOR FOUNDATIONS HAVE NO INDENTATIONS OR CRACKS

A

DETAILED
CLOSE
VISUAL

22
Q

TABLE 1 Ex d

A.30
MOTOR VENTILATION AIRFLOW ARE NOT IMPEDED

A

DETAILED
CLOSE
VISUAL

23
Q

TABLE 1 Ex d

A.31
INSULATION RESISTANCE (IR) OF THE MOTOR WINDINGS IS SATISFACTORY
24
Q

TABLE 1 Ex d

B.1
TYPE OF CABLE IS APPROPRIATE

25
TABLE 1 Ex d B.2 THERE IS NO OBVIOUS DAMAGE TO CABLES
DETAILED CLOSE VISUAL
26
TABLE 1 Ex d B.3 SEALING OF TRUNKING, DUCTS, PIPES, CONDUITS IS SATISFACTORY
DETAILED CLOSE VISUAL
27
TABLE 1 Ex d B.4 STOPPING BOXES AND CABLE BOXES ARE CORRECTLY FILLED.
DETAILED
28
TABLE 1 Ex d B.5 INTEGRITY OF CONDUIT SYSTEM AND INTERFACE WITH MIXED SYSTEM IS MAINTAINED
DETAILED
29
TABLE 1 Ex d B.6 EARTH CONNECTIONS, INCLUDING ANY SUPPLEMENTARY EARTHING BONDING CONNECTIONS ARE SATISFACTORY (CONNECTIONS ARE CLEAN AND TIGHT AND CONDUCTORS ARE OF SUFFICIENT CROSS-SECTION) - PHYSICAL CHECK
DETAILED
30
TABLE 1 Ex d B.6 EARTH CONNECTIONS, INCLUDING ANY SUPPLEMENTARY EARTHING BONDING CONNECTIONS ARE SATISFACTORY (CONNECTIONS ARE CLEAN AND TIGHT AND CONDUCTORS ARE OF SUFFICIENT CROSS-SECTION) - VISUAL CHECK
CLOSE | VISUAL
31
TABLE 1 Ex d B.7 FAULT LOOP IMPEDANCE (TN SYSTEMS) OR EARTHING RESISTANCE (IT SYSTEMS) IS SATISFACTORY.
DETAILED
32
TABLE 1 Ex d B.8 AUTOMATIC ELECTRICAL PROTECTIVE DEVICES ARE SET CORRECTLY (AUTO-RESET NOT POSSIBLE)
DETAILED
33
TABLE 1 Ex d B.9 AUTOMATIC ELECTRICAL PROTECTIVE DEVICES OPERATE WITHIN PERMITTED LIMITS.
DETAILED
34
TABLE 1 Ex d B.10 SPECIFIC CONDITIONS OF USE (IF APPLICABLE) ARE COMPLIED WITH.
DETAILED
35
TABLE 1 Ex d B.11 CABLES NOT IN USE ARE CORRECTLY TERMINATED
DETAILED
36
TABLE 1 Ex d ``` B.12 OBSTRUCTIONS ADJACENT TO FLAMEPROOF FLANGED JOINTS ARE IN ACCORDANCE TO IEC 60079-14 IIA 10mm IIB 30mm IIC 40mm ```
DETAILED CLOSE VISUAL
37
TABLE 1 Ex d B.13 VARIABLE VOLTAGE / FREQUENCY INSTALLATIONS IN ACCORDANCE WITH DOCUMENTATION
DETAILED | CLOSE
38
TABLE 1 Ex d C.1 EQUIPMENT IS ADEQUATELY PROTECTED AGAINST CORROSION, WEATHER, VIBRATION AND OTHER ADVERSE VIBRATION AND OTHER ADVERSE FACTORS.
DETAILED CLOSE VISUAL
39
TABLE 1 Ex d C.2 NO UNDUE ACCUMULATION OF DUST AND DIRT
DETAILED CLOSE VISUSL
40
Levels of Protection What is the assured level of protection for Equipment Group II 1G 1D
II 1G 1D | Level of protection assured in the event of two equipment faults occurring independently of each other.
41
Levels of Protection What is the assured level of protection for Equipment Group II 2G 2D
II 2G 2D | Level of protection assured in the event of one equipment fault.
42
Levels of Protection What is the level of assured protection for Equipment Group II 3G 3D
II 3G 3D | Level of protection is assured in normal operation
43
DUST GROUP What is the definition of Group IIIA
IIIA is combustible flying dust and fibres Saw Dust Grain Dust Tobacco
44
DUST GROUP What is the definition of Group IIIB
IIIB is non-conductive dust. Creates an electrostatic Charge Milk Powder Sugar Powder
45
DUST GROUP What is the definition of Group IIIC
IIIC is conductive dust. Most Dangerous Dust type Graphite Dust Metal Dust Toner
46
What are the three grades of inspection?
VISUAL CLOSE DETAILED