COMPEX Ex d Inspection Flashcards

1
Q

TABLE 1 Ex d

A.1
EQUIPMENT IS APPROPRIATE TO THE EPL/ZONE REQUIREMENTS OF THE LOCATION.

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

TABLE 1 Ex d

A.2
EQUIPMENT GROUP IS CORRECT

A

DETAILED
CLOSE

Equipment Groups
Group Category Level of protection
Group I M1 Very High
Group I M2 High

Group II CAT 1 Very High
Group II CAT 2 High
Group II CAT 3 Normal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

TABLE 1 Ex d

A.3
EQUIPMENT TEMPERATURE CLASS IS CORRECT (GAS ONLY)

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

TABLE 1 Ex d

A.5
DEGREE OF PROTECTION (IP) OF EQUIPMENT IS APPROPRIATE FOR THE LEVEL OF PROTECTION/GROUP CONDUCTIVITY

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

TABLE 1 Ex d

A.6
EQUIPMENT CIRCUIT IDENTIFICATION IS CORRECT.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

TABLE 1 Ex d

A.7
EQUIPMENT CIRCUIT IDENTIFICATION IS AVAILABLE.

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

TABLE 1 Ex d

A.8
ENCLOSURE, GLASS PARTS AND GLASS TO METAL SEALING GASKETS AND / OR COMPOUNDS ARE SATISFACTORY.

A

DETAILED
CLOSE
VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

TABLE 1 Ex d

A.9
THERE IS NO DAMAGE OR UNAUTHORISED MODIFICATIONS

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

TABLE 1 Ex d

A.10
THERE IS NO EVIDENCE OF UNAUTHORISED MODIFICATIONS

A

CLOSE

VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

TABLE 1 Ex d

A.11
BOLTS, CABLE ENTRY DEVICES (DIRECT AND INDIRECT) AND BLANKING ELEMENTS ARE OF THE CORRECT TYPE ARE COMPLETE AND TIGHT.
PHYSICAL CHECK

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

TABLE 1 Ex d

A.11
BOLTS, CABLE ENTRY DEVICES (DIRECT AND INDIRECT) AND BLANKING ELEMENTS ARE OF THE CORRECT TYPE ARE COMPLETE AND TIGHT.

A

VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

TABLE 1 Ex d

A.12
THREADED COVERS ON ENCLOSURES ARE OF THE CORRECT TYPE, ARE TIGHT AND SECURED.
PHYSICAL CHECK

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

TABLE 1 Ex d

A.12
THREADED COVERS ON ENCLOSURES ARE OF THE CORRECT TYPE, ARE TIGHT AND SECURED.

A

VISUAL

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

TABLE 1 Ex d

A.13
JOINT FACES ARE CLEAN AND UNDAMAGED AND GASKETS, IF ANY, ARE SATISFACTORY.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

TABLE 1 Ex d

A.14
CONDITION OF ENCLOSURE GASKETS IS SATISFACTORY.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

TABLE 1 Ex d

A.15
THERE IS NO EVIDENCE OR INGRESS OF WATER OR DUST IN THE ENCLOSURE IN ACCORDANCE WITH THE IP RATING.

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

TABLE 1 Ex d

A.16
DIMENSIONS OF FLANGE JOINT GAPS ARE WITHIN MAXIMUM VALUES PERMITTED

A

DETAILED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

TABLE 1 Ex d

A.25
BREATHING AND DRAINING DEVICES ARE SATISFACTORY.

A

DETAILED

CLOSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

TABLE 1 Ex d

A.27
HIGH INTENSITY DISCHARGE LAMPS ARE NOT INDICATING END OF LIFE EFFECTS

A

DETAILS
CLOSE
VISUAL

20
Q

TABLE 1 Ex d

A.28
LAMP TYPE, RATING, PIN CONFIGURATION AND POSITION ARE CORRECT

A

DETAILED

21
Q

TABLE 1 Ex d

A.29
MOTOR FANS HAVE SUFFICIENT CLEARANCE TO ENCLOSURE AND / OR COVERS, COOLING SYSTEMS ARE UNDAMAGED, MOTOR FOUNDATIONS HAVE NO INDENTATIONS OR CRACKS

A

DETAILED
CLOSE
VISUAL

22
Q

TABLE 1 Ex d

A.30
MOTOR VENTILATION AIRFLOW ARE NOT IMPEDED

A

DETAILED
CLOSE
VISUAL

23
Q

TABLE 1 Ex d

A.31
INSULATION RESISTANCE (IR) OF THE MOTOR WINDINGS IS SATISFACTORY
A

DETAILED

24
Q

TABLE 1 Ex d

B.1
TYPE OF CABLE IS APPROPRIATE

A

DETAILED

25
Q

TABLE 1 Ex d

B.2
THERE IS NO OBVIOUS DAMAGE TO CABLES

A

DETAILED
CLOSE
VISUAL

26
Q

TABLE 1 Ex d

B.3
SEALING OF TRUNKING, DUCTS, PIPES, CONDUITS IS SATISFACTORY

A

DETAILED
CLOSE
VISUAL

27
Q

TABLE 1 Ex d

B.4
STOPPING BOXES AND CABLE BOXES ARE CORRECTLY FILLED.

A

DETAILED

28
Q

TABLE 1 Ex d

B.5
INTEGRITY OF CONDUIT SYSTEM AND INTERFACE WITH MIXED SYSTEM IS MAINTAINED

A

DETAILED

29
Q

TABLE 1 Ex d

B.6
EARTH CONNECTIONS, INCLUDING ANY SUPPLEMENTARY EARTHING BONDING CONNECTIONS ARE SATISFACTORY (CONNECTIONS ARE CLEAN AND TIGHT AND CONDUCTORS ARE OF SUFFICIENT CROSS-SECTION) - PHYSICAL CHECK

A

DETAILED

30
Q

TABLE 1 Ex d

B.6
EARTH CONNECTIONS, INCLUDING ANY SUPPLEMENTARY EARTHING BONDING CONNECTIONS ARE SATISFACTORY (CONNECTIONS ARE CLEAN AND TIGHT AND CONDUCTORS ARE OF SUFFICIENT CROSS-SECTION) - VISUAL CHECK

A

CLOSE

VISUAL

31
Q

TABLE 1 Ex d

B.7
FAULT LOOP IMPEDANCE (TN SYSTEMS) OR EARTHING RESISTANCE (IT SYSTEMS) IS SATISFACTORY.

A

DETAILED

32
Q

TABLE 1 Ex d

B.8
AUTOMATIC ELECTRICAL PROTECTIVE DEVICES ARE SET CORRECTLY (AUTO-RESET NOT POSSIBLE)

A

DETAILED

33
Q

TABLE 1 Ex d

B.9
AUTOMATIC ELECTRICAL PROTECTIVE DEVICES OPERATE WITHIN PERMITTED LIMITS.

A

DETAILED

34
Q

TABLE 1 Ex d

B.10
SPECIFIC CONDITIONS OF USE (IF APPLICABLE) ARE COMPLIED WITH.

A

DETAILED

35
Q

TABLE 1 Ex d

B.11
CABLES NOT IN USE ARE CORRECTLY TERMINATED

A

DETAILED

36
Q

TABLE 1 Ex d

B.12
OBSTRUCTIONS ADJACENT TO FLAMEPROOF FLANGED JOINTS ARE IN ACCORDANCE TO IEC 60079-14    
IIA    10mm
IIB     30mm
IIC     40mm
A

DETAILED
CLOSE
VISUAL

37
Q

TABLE 1 Ex d

B.13
VARIABLE VOLTAGE / FREQUENCY INSTALLATIONS IN ACCORDANCE WITH DOCUMENTATION

A

DETAILED

CLOSE

38
Q

TABLE 1 Ex d

C.1
EQUIPMENT IS ADEQUATELY PROTECTED AGAINST CORROSION, WEATHER, VIBRATION AND OTHER ADVERSE VIBRATION AND OTHER ADVERSE FACTORS.

A

DETAILED
CLOSE
VISUAL

39
Q

TABLE 1 Ex d

C.2
NO UNDUE ACCUMULATION OF DUST AND DIRT

A

DETAILED
CLOSE
VISUSL

40
Q

Levels of Protection

What is the assured level of protection for Equipment Group II 1G 1D

A

II 1G 1D

Level of protection assured in the event of two equipment faults occurring independently of each other.

41
Q

Levels of Protection

What is the assured level of protection for Equipment Group II 2G 2D

A

II 2G 2D

Level of protection assured in the event of one equipment fault.

42
Q

Levels of Protection

What is the level of assured protection for Equipment Group II 3G 3D

A

II 3G 3D

Level of protection is assured in normal operation

43
Q

DUST GROUP

What is the definition of Group IIIA

A

IIIA is combustible flying dust and fibres

Saw Dust
Grain Dust
Tobacco

44
Q

DUST GROUP

What is the definition of Group IIIB

A

IIIB is non-conductive dust.

Creates an electrostatic Charge

Milk Powder
Sugar Powder

45
Q

DUST GROUP

What is the definition of Group IIIC

A

IIIC is conductive dust.

Most Dangerous Dust type

Graphite Dust
Metal Dust
Toner

46
Q

What are the three grades of inspection?

A

VISUAL
CLOSE
DETAILED