COMPEX Ex e n Inspection Flashcards
TABLE 1 Ex e n
A.1
EQUIPMENT IS APPROPRIATE TO THE EPL/ZONE REQUIREMENTS OF THE LOCATION.
DETAILED
CLOSE
VISUAL
TABLE 1 Ex e n
A.2
EQUIPMENT GROUP IS CORRECT
DETAILED
CLOSE
TABLE 1 Ex e n
A.3
EQUIPMENT TEMPERATURE CLASS IS CORRECT (GAS ONLY)
DETAILED
CLOSE
TABLE 1 Ex e n
A.4
EQUIPMENT MAXIMUM SURFACE TEMPERATURE IS CORRECT (DUST ONLY)
DETAILED
CLOSE
TABLE 1 Ex e n
A.5
DEGREE OF PROTECTION (IP) OF EQUIPMENT IS APPROPRIATE FOR THE LEVEL OF PROTECTION/GROUP CONDUCTIVITY
DETAILED
CLOSE
VISUAL
TABLE 1 Ex e n
A.6
EQUIPMENT CIRCUIT IDENTIFICATION IS CORRECT.
DETAILED
TABLE 1 Ex e n
A.7
EQUIPMENT CIRCUIT IDENTIFICATION IS AVAILABLE.
DETAILED
CLOSE
VISUAL
TABLE 1 Ex e n
A.8
ENCLOSURE, GLASS PARTS AND GLASS TO METAL SEALING GASKETS AND / OR COMPOUNDS ARE SATISFACTORY.
DETAILED
CLOSE
VISUAL
TABLE 1 Ex e n
A.9
THERE IS NO DAMAGE OR UNAUTHORISED MODIFICATIONS
DETAILED
TABLE 1 Ex e n
A.10
THERE IS NO EVIDENCE OF UNAUTHORISED MODIFICATIONS
CLOSE
VISUAL
TABLE 1 Ex e n
A.11
BOLTS, CABLE ENTRY DEVICES (DIRECT AND INDIRECT) AND BLANKING ELEMENTS ARE OF THE CORRECT TYPE ARE COMPLETE AND TIGHT.
PHYSICAL CHECK
DETAILED
CLOSE
TABLE 1 Ex e n
A.11
BOLTS, CABLE ENTRY DEVICES (DIRECT AND INDIRECT) AND BLANKING ELEMENTS ARE OF THE CORRECT TYPE ARE COMPLETE AND TIGHT.
VISUAL CHECK
VISUAL
TABLE 1 Ex e n
A.14
CONDITION OF ENCLOSURE GASKETS IS SATISFACTORY.
DETAILED
TABLE 1 Ex e n
A.15
THERE IS NO EVIDENCE OR INGRESS OF WATER OR DUST IN THE ENCLOSURE IN ACCORDANCE WITH THE IP RATING.
DETAILED
TABLE 1 Ex e n
A.17
ELECTRICAL CONNECTIONS ARE TIGHT
DETAILED