COMPEX Ex i nL Inspection Flashcards
TABLE 2 Ex i nL
A.1
CIRCUIT AND / OR EQUIPMENT DOCUMENTATION IS APPROPRIATE TO THE EPL/ / ZONE REQUIREMENTS.
DETAILED
CLOSE
VISUAL
TABLE 2 Ex i nL
A.2
EQUIPMENT INSTALLED IS THAT SPECIFIED IN THE DOCUMENTATION.
DETAILED
CLOSE
TABLE 2 Ex i nL
A.3
CIRCUIT AND / OR EQUIPMENT CATEGORY AND GROUP CORRECT
DETAILED
CLOSE
TABLE 2 Ex i nL
A.4
IP RATING OF EQUIPMENT IS APPROPRIATE TO THE GROUP III MATERIAL PRESENT.
DETAILED
CLOSE
TABLE 2 Ex i nL
A.5
EQUIPMENT TEMPERATURE CLASS IS CORRECT
DETAILED
CLOSE
TABLE 2 Ex i nL
A.6
AMBIENT TEMPERATURE RANGE OF THE APPARATUS IS CORRECT FOR THE INSTALLATION.
DETAILED
CLOSE
TABLE 2 Ex i nL
A.7
SERVICE TEMPERATURE RANGE OF THE EQUIPMENT IS CORRECT FOR THE INSTALLATION
DETAILED
CLOSE
TABLE 2 Ex i nL
A.8
INSTALLATION IS CLEARLY LABELLED
DETAILED
CLOSE
TABLE 2 Ex i nL
A.9
ENCLOSURE, GLASS PARTS AND GLASS TO METAL SEALING GASKETS AND / OR COMPOUNDS ARE SATISFACTORY.
DETAILED
TABLE 2 Ex i nL
A.10
CABLE GLANDS AND BLANKING ELEMENTS ARE THE CORRECT TYPE, COMPLETE AND TIGHT. - PHYSICAL CHECK
DETAILED
CLOSE
TABLE 2 Ex i nL
A.10
CABLE GLANDS AND BLANKING ELEMENTS ARE THE CORRECT TYPE, COMPLETE AND TIGHT. - VISUAL CHECK
VISUAL
TABLE 2 Ex i nL
A.11
THERE ARE NO UNAUTHORISED MODIFICATIONS
DETAILED
TABLE 2 Ex i nL
A.12
THERE IS NO EVIDENCE OF UNAUTHORISED MODIFICATIONS
CLOSE
VISUAL
TABLE 2 Ex i nL
A.13
DIODE SAFETY BARRIERS, GALVANIC ISOLATORS, RELAYS AND OTHER ENERGY LIMITING DEVICES ARE OF THE APPROVED TYPE, INSTALLED IN ACCORDANCE WITH THE CERTIFICATION REQUIREMENTS AND SECURELY EARTHED WHERE REQUIRED
DETAILED
CLOSE
VISUAL
TABLE 2 Ex i nL
A.14
CONDITION OF ENCLOSURE GASKETS IS SATISFACTORY
DETAILED