Tech Specs Flashcards

Reactivity Control and Power Distribution Limits

1
Q

3.1.1 Shutdown Margin

List LCOs and Applicability

A

LCO

SDM Shall Be:
A. >= 0.38% dk/k with the highest worth control rod analytically determined; or
B. >= 0.28% dk/k with the highest worth control rod determined by test.

Applicability: Modes 1-5

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

3.1.1 Shutdown Margin

List all conditions that require action in 1 hour or less.

A

SDM Not within Limits

Mode 3:
Insert all insertable control rods.

Mode 4:
Insert all insertable control rods
Initiate action to restore primary containment to OPERABLE
Initiate action to restore isolation capability in each required primary containment penetration flow path not isolated
Initiate action to close one door in each primary containment air lock

Mode 5:
Suspend CORE ALTS except for control rod insertion and fuel assembly removal.
Initiate action to insert all insertable control rods in core cells containing one or more control rods.
Initiate action to restore primary containment to OPERABLE
Initiate action to restore isolation capability in each required primary containment penetration flow path not isolated
Initiate action to close one door in each primary containment air lock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

3.1.1 SDM Bases

What are the 3 reasons for having SDM requirements?

A

1. Reactor can be made subcritical from all operating conditions and transients and Design Basis Events.

2. Reactivity transients associated with postulatd accident conditions are controllable within acceptable limits.

3. The reactor will be maintained sufficiently subcritical to preclude inadvertant criticality in the shutdown condition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

3.1.1 SDM Bases

Regarding safety analysis, what does an adequate SDM provide?

A

Adequate SDM provides assurance that inadvertant criticalities and potential rod drop accidents involving high worth control rods (namely the first control rod withdrawn) will not cause significant fuel damage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

3.1.1 SDM Bases

Discuss the difference between analytical and tested values of SDM.

A

Tested values are representative of the actual configuration. Uncertainty exists in design calculations that are accounted for with the extra value.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

3.1.1 SDM Bases

Discuss the bases of the applicability requirements for SDM.

A

Modes 1 & 2 the SDM must be provided because subcriticality with the highest worth control rod withdrawn is assumed in the rod drop accident.

In modes 3 & 4, SDM is required to ensure the reactor will be maintained subcritical with margin for a single withdrawn control rod.

Mode 5 is to prevent inadvertant criticality during the withdrawal of a single control rod from a core cell containing one or more fuel assemblies.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

3.1.2 Reactivity Anomalies

List LCOs and applicabilities

A

LCO
The reactivity difference between the monitored rod density and the predicted rod density shall be within +/- 1% dk/k.

Applicability
Modes 1 & 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

3.1.2 Reactivity Anamolies Bases

Why is the reactivity anamoly LCO established?

A

Ensure plant operation is maintained within the assumptions of the safety analysis.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

3.1.2 Reactivity Anamolies Bases

Discuss the importance of a 1% deviation in predicted to actual reactivity.

A

> 1% difference is considered larger than expected and should be evaluated. Accurate prediction of reactivity is an implicit and explicit part of safety analysis calculations.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

3.1.3 Control Rod Operability

List LCOs and Applicabilities

Are there any notes associated with this LCO?

A

LCO
Each control rod shall be operable.

Applicability
Modes 1 & 2

Notes
Separate Condition entry is allowed for each control rod.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

3.1.3 Control Rod Operability

What 1hr or less actions are associated with this LCO?

A

Condition One withdrawn control rod stuck.

Action
Immediately: Verify stuck control rod separation criteria are met.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

3.1.3 Control Rod Operability Bases

From a safety analysis standpoint, what does insertion of control rods provide?

A

Assurance that the assumptions for scram reactivity in the DBA and transient analysis are not violated.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

3.1.3 Control Rod Operability Bases

What major factors are considered when determining control rod operability?

A

Scram Insertion Times, Control Rod Coupling Integrity, and Control Rod Position Indication.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

3.1.3 Control Rod Operability Bases

When is a control rod considered stuck?

A

Considered stuck if it will not insert (using all available methods of insertion) by either CRD drive water or scram pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

3.1.3 Control Rod Operability Bases

Regarding stuck control rods, what is separation criteria?

A

There are two different separation criterias established in 3.1.3 Bases
Slow and stuck control rods, and Bank Position W/D Sequence

For stuck control rods and slow control rods

A stuck control rod may not occupy a location adjacent to a “slow” control rod.

Regarding BPWS
Control rods not in compliance with BPWS must be separated by at least two OPERABLE control rods in all directions, including diagonal. This is only applicable <= 19% RTP.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

3.1.3 Control Rod Operability Bases

Discuss the requirements when a large amount of control rods are INOPERABLE. What is the basis of this criteria?

A

When 9 or more control rods are inoperable, a mode change to Mode 3 is required.

The occurrence of a large number of inoperable control rods is indicative of a larger problem, and the control rods should be placed in a position where a scram is not required.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

3.1.4 Control Rod Scram Times

List the LCOs and Applicabilities

A

LCO

A. No more than 13 OPERABLE control rods shall be slow IAW Table 3.1.4-1 AND

B. No OPERABLE control rod that is slow shall occupy a location adjacent to another OPERABLE control rod that is “slow” or a withdrawn control rod that is stuck.

Applicability
Modes 1, 2

18
Q

3.1.4 Control Rod Scram Times

What is the criteria for a control rod to be considered slow?

Review the table attached.

A

Based on certain steam dome pressures, there is a maximum time from different notch positions. If the control rod does not fully insert from these positions in this time, the rod is considered slow.

19
Q

3.1.4 Control Rod Scram Times

How slow can a control rod be before it is considered INOPERABLE?

What actions are required for a control rod that meets this criteria?

A

Any rod that takes longer than 7 seconds to scram is considered INOP.

Enter required actions for LCO 3.1.3 “Control Rod Operability”

20
Q

3.1.4 Control Rod Scram Times Bases

What does the Scram function of the CRD system protect?

How does this change with Reactor pressure?

What do these protected features ensure?

A

Protects the MCPR Safety Limit and the 1% cladding plastic strain fuel design limit. (MCPR, LHGR, APLHGR).

Above 950 psig, the scram function is designed to insert negative reactivity at a rate fast enough to prevent the actual MCPR from becoming less than the MCPR Safety Limit during the analyzed limiting power transient.

Below 950 psig, the scram function is assumed to perform during the control rod drop accident, and, therefore, also provides protection against violating fuel damage limits during reactivity insertion accidents.

Ensures no fuel damage will occur if these limits are not exceeded.

21
Q

3.1.4 Control Rod Scram Times Bases

How are scram times classified as slow for intermediate steam dome pressures?

A

Linear Interpolation.

22
Q

3.1.5 Control Rod Scram Accumulators

List the LCO and Applicabilities.

What actions have requirements of 1 hour or less?

A

LCO
Each control rod scram accumulator shall be OPERABLE.

Applicability
Modes 1 & 2

NOTE
Separate condition entry is allowed for each control rod scram accumulator

1 Hour or Less Actions
For Action B
When steam dome pressure is > 600 psig and two or more scram accumulators are inoperable, complete the following:
Within 20 Minutes from discovery of entry into condition, restore charging water header pressure to >= 1520 psig.
AND
Within 1 hour-
Declare the associated control rod scram time as “slow”.
Note: This action is only applicable if the associated control rod scram time was satisfactory in the most recent scram time test.
*OR

Declare the associated control rod inoperable.

For Action C
With steam dome pressure < 600 psig, if charging water header pressure is < 1520 psig, immediately verify all control rods associated with inoperable accumulators are fully inserted

AND

Within 1 hour, declare the associated control rods inoperable.

For Action D
If the required actions of Action B.1 or C.1 are not met, immediately place the mode switch in shutdown.
Note: This requirement is not applicable if all control rods associated with inoperable accumulators are already fully inserted.

23
Q

3.1.5 Control Rod Scram Accumulators Bases

Why is the operability of the scram accumulators required and what determines their operability?

A

Ensures that adequate scram insertion capability exists when needed over the entire range of reactor pressures.

Operability is based on maintaining adequate accumulator pressure.

24
Q

3.1.6 Control Rod Pattern

List the LCO and Applicability.

What 1 Hour or less actions are associated with this LCO?

A

LCO
Operable control rods shall comply with the requirements of the banked position withdrawal sequence.

Applicability
Modes 1 & 2 at RTP <= 19%.

1 Hour or less actions
Action B
With 9 or more operable control rods not in compliance of the BPWS, immediately suspend withdrawal of control rods and place the mode switch in shutdown within 1 hour.

25
Q

3.1.6 Control Rod Pattern Bases

Why is there a withdrawal pattern?

A

The Rod Drop Accident analyses assume that the operator follows a prescribed withdrawal sequence. These sequences define the initial conditions for the analysis. The rod pattern controller provides a backup to the operator to ensure these conditions are not violated.

26
Q

3.1.6 Control Rod Pattern Bases

What is ensured by the limits established in the design basis of the control rod drop accident?

A

Peak fuel energy deposition of <= 280 cal/gm ensures that the resulting pressure transient will be less than the ASME code limits and calculated offsite doses will be well within the required limits.

27
Q

3.1.6 Control Rod Pattern Bases

How does the BPWS work?

A

Control rods are required to be moved in groups, with all control rods assigned to a specific group required to be within specified banked positions.

A rod out of pattern will result in a rod block.

28
Q

3.1.6 Control Rod Pattern Bases

What is the basis of the RTP requirement of this LCO?

A

In Modes 1 & 2, when RTP is <= 19%, the CRDA is a design basis accident. Compliance with the assumptions is required.

When power is > 19%, there is no credible control rod configuration that results in a control rod worth that could exceed the 280 cal/gm fuel damage limit during a CRDA.

29
Q

3.1.7 Standby Liquid Control System

List the LCO and Applicability

A

LCO
Two SLC systems shall be operable.

Applicability
Modes 1 & 2

30
Q

3.1.7 SLC System Bases

What does the operability of the SLC system provide?

A

Provides backup capability of reactivity control in the event that control rods can not be fully inserted.

31
Q

3.1.7 SLC System Bases

What are the requirements for the SLC system to be operable?

A

SLC Pumps develop >= 32.4 gpm flow rate with discharge pressure >= 1220 psig.

Boric acid concentration is within established limits IAW table.

SLC storage tank >= 70F

Continuity of explosive charges for squib valves exists.

All valves in their proper position and valves operate correctly.

32
Q

3.1.8 Scram Discharge Volume Vent and Drain Valves

List the LCO and Applicability

A

LCO
Each SDV vent and drain valve shall be operable.

Applicability
Modes 1 & 2

Notes
Separate entry conditions allowed for each SDV vent and drain valve.
An isolate line may be unisolated under admnistrative control to allow draining and venting of the SDV.

33
Q

3.1.8 SDV bases

What is the basis of requiring operability of the SDV vent and drain valves?

A

If the SDV vent and drain valves did not close when required, a direct path from Rx to containment atmosphere would exist.

If the valves are required to be open when a scram is not inserted to ensure there is sufficient volume to receive the discharge from the scram insertion.

34
Q

3.2.1 APLHGR

List the LCO and Applicability

A

LCO
All APLHGRs shall be less than or equal to the limits specified in the COLR.

Applicability
Greater than or equal to 23.8% RTP

35
Q

3.2.1 APLHGR Bases

What is APLHGR?

What does the limit protect?

A

APLHGR (Average Planar Linear Heat Generation Rate) is a measure of average Linear Heat Generation Rate of all fuel rods in all fuel assemblies at all locations.

The limit ensures that peak cladding temperature does not exceed 2200F during the postulated design basis LOCA, thereby maintaining fuel cladding below the maximum oxidation limits.

36
Q

3.2.2 MCPR

List the LCO and Applicability

A

LCO
All MCPRs shall be greater than or equal to the MCPR operating limits specified in the COLR.

Applicability
Greater than or equal to 23.8% RTP

37
Q

3.2.2 MCPR Bases

What does compliance with the MCPR operating limit ensure?

A

Compliance with MCPR ensures that no fuel damage results during anticipated operational occurences and that 99.9% of fuel rods avoid transition boiling if the limit is not violated.

38
Q

3.2.2 MCPR Bases

What transients were evaluated to determine MCPR?

A

Loss of flow, increase in pressure in power, positive reactivity insertion, and coolant temperature decrease.

39
Q

3.2.2 MCPR Bases

How is the MCPR operating limit determined?

A

Determined by the larger of the MCPR(flow) and MCPR(power) limits, which are based on the MCPR(99.9%) limit specified in the COLR.

40
Q

3.2.3 LHGR

List the LCO and Applicability

A

LCO
All LHGRs shall be less than or equal to the limits specified in the COLR.

Applicability
Greater than or equal to 23.8% RTP.

41
Q

3.2.3 LHGR Bases

What is the purpose of the LHGR thermal limit?

A

Ensure that fuel design limits are not exceeded anywhere in the core during normal operation, including anticipated operational occurrences, and to ensure that peak cladding temperature < 2200F during DBA.

Ensures that the 1% fuel cladding strain design limit is not exceeded during continuous operation with HFGR up to the operating limit LHGR specified in the COLR.