SO: Seal Oil Flashcards

1
Q

From where does the ESOP take a suction?

A

The return header not the Vacuum Tank. The Vacuum Tank will fill and LCV-25 in the tank will close.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens to the Seal Oil System when MTLO is lost?

A

The Aux Detraining Tank will drain to the Vacuum Tank. The MTLO pressure will no longer hold the check valves closed which effectively makes the SO System a closed system which results in heatup.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What powers the ESOP?

A

NK

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When will the ESOP trip?

A

It wont. There are electrical protection alarms but wont trip.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How much can H2 purity lower if vacuum is not maintained in the Vacuum Tank?

A

2% every eight hours.

The air and/or Hydrogen from the oil will be released in the Main Generator.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What prevents both filters from being in service at the same time?

A

A mechanical interlock

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the purpose for the Vacuum Tank in the Seal Oil System?

A

To maintain H2 purity

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

After the Main Seal Oil pumps, what is the flow path to the Main Generator? (Big Picture)

A

The line splits into 2 lines downstream of the filters and goes to the Turbine End of the MG and the Collector End of the MG.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When does the ESOP auto start?

A

Main Seal Oil Pump Discharge of 110 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the power supply to the Main Seal Oil Pumps?

A

NG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the purpose for the SO Recirc Pump?

A

Removes gases from the Seal Oil

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is normal discharge pressure for the Main Seal Oil Pump?

A

About 120 psig

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

To where does the seal oil flowing inboard from the shaft seals?

A

To the hydrogen detraining section and then down to the float valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

PDCV- ___ maintains ___ psid between H2 pressure in the Main Generator and the Main Seal Oil Pump discharge pressure.

A

PDCV-10

8 psid

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How is vacuum maintained in the Vacuum Tank for the Seal Oil System?

A

A Vacuum Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

If you receive the SO/H2 DP LO Alarm, what does that signify?

A

That H2 is escaping from the Main Generator to atmosphere.

17
Q

Describe the normal flow path for Seal Oil.

A
Vacuum Tank
MSOP
PDCV-10
MG Seals
H2 and Aux Detaining Tanks
MTLO Reservior
18
Q

What happens to SO if you lose the MSOP and the ESOP?

A

MTLO will supply at about 25psig. Hydrogen pressure in the Main Generator will drop a few pounds lower than the MTLO pressure i.e. H2 leaks out = fire hazard

19
Q

What will happen if the Vacuum Tank in the Seal Oil System becomes inperable?

A

H2 purity will decrease

2% every 8 hours

20
Q

When would one need to bypass the float valve in the Seal Oil System?

A

On a high level in the detraining section.

21
Q

What powers the SO Recirc Pump?

A

NG

22
Q

If you lose the MSOP and the ESOP, how does that affect Main Generator operation?

A

The MTLO supply pressure of ~25 psig which means that H2 pressure will drop lower than that. Main Generator load will need to be reduced.

23
Q

What is the flow path for SO Recirc Pump?

A

Takes a suction on the Vacuum Tank and returns the flow to the Vacuum Tank through spray nozzles

24
Q

Can the float valve, LCV-24, in the Seal Oil System be bypassed?

A

Yes

25
Q

At what vacuum is the Vacuum Tank maintained for the Seal Oil System?

A

1” HgA