Is the IA System safety related?
No
What is the power supply to the IA Compressors?
NG
PVNGS has ___ compressors that can provide _____% capacity each.
3
100%
What is the IA pressure requirement to operate components?
80 psig
What is the backup supply to IA? When does it open?
N2
85 psig
How many air compressors are normally running?
1
What cools the IA Compressors normally?
TC
What cools the IA Compressors during an outage?
DS
What will isolate IA to containment?
CSAS
If IAA-UV-2 closed automatically, can it be overridden?
Yes
What position does IAA-UV-2 fail?
Closed on a loss of power (PKA)
IA Receivers are sized to provide _____ seconds of storage.
30 seconds
How often does the IA Master Controller cycle IA Compressors?
Once a week
What is the normal IA band?
109 psig - 119 psig
At _____ psig the delay timer is used to determine if additional IA Compressors need to be loaded.
109 psig