NN: Non-Class 120 VAC Flashcards
Which NN buses are grounded and which are ungrounded?
NNN-D11 and NNN-D12 are ungrounded
NNN-D15 and NNN-D16 are grounded
What are the normal and backup power supplies for NNN-D11 and NNN-D12?
Normal: Non-Class MCC through a Voltage Regulator
Backup: Class MCC
What are the normal and backup power supplies for NNN-D15 and NNN-D16?
Normal: Non-Class MCC through a Voltage Regulator
Backup: SIAS Load Shed Panel
- Except D16 for Unit 3 which is a Class MCC
Are the ABTs Power Seeking or Normal Seeking?
Power Seeking
What will be the status of the NN buses if a SIAS + LOP were to occur?
NNN-D11 - Transferred to Class MCC Backup
NNN-D12 - Transferred to Class MCC Backup
NNN-D15 - de-energized
NNN-D16 - U1 and U2 - de-energized
NNN-D16 - U3 - Transferred to Class MCC Backup
Which NN buses have ground detectors?
NNN-D11 and NNN-D12
What indications are there for a ground on an NN bus?
- A local red light
- A Control Room Alarm
What would bring in the Common Control Room trouble alarm for NN?
- A Ground on NNN-D11/12
- Loss of backup power on SIAS