NN: Non-Class 120 VAC Flashcards

1
Q

Which NN buses are grounded and which are ungrounded?

A

NNN-D11 and NNN-D12 are ungrounded

NNN-D15 and NNN-D16 are grounded

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the normal and backup power supplies for NNN-D11 and NNN-D12?

A

Normal: Non-Class MCC through a Voltage Regulator
Backup: Class MCC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the normal and backup power supplies for NNN-D15 and NNN-D16?

A

Normal: Non-Class MCC through a Voltage Regulator
Backup: SIAS Load Shed Panel
- Except D16 for Unit 3 which is a Class MCC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Are the ABTs Power Seeking or Normal Seeking?

A

Power Seeking

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What will be the status of the NN buses if a SIAS + LOP were to occur?

A

NNN-D11 - Transferred to Class MCC Backup
NNN-D12 - Transferred to Class MCC Backup
NNN-D15 - de-energized
NNN-D16 - U1 and U2 - de-energized
NNN-D16 - U3 - Transferred to Class MCC Backup

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Which NN buses have ground detectors?

A

NNN-D11 and NNN-D12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What indications are there for a ground on an NN bus?

A
  • A local red light

- A Control Room Alarm

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What would bring in the Common Control Room trouble alarm for NN?

A
  • A Ground on NNN-D11/12

- Loss of backup power on SIAS

How well did you know this?