Sizing Vents And Chimneys Flashcards

1
Q

Carbon dioxide spilled in the area of appliances will enter the combustion zone and create what

A

Carbon monoxide

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What category are Appliances having draft hoods

A

Category 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Atmospheric pressure inside buildings have category one appliances installed must not be allowed to drop more than

A

5 pascal or .02” water column

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Minimum dimension of vent or chimney that is not round ?

and the minimum area of the vent shall be equal to that of what size

A

2”
3”

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

A vent connecter that serves a single appliance with multiple draft hoods or flu gas outlets will be sized how

A

ROT/ the vent connecter will have an area equal to the combined area of all appliance outlets

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What column in the tables must be used to size a vent or chimney installed in an airtight building?

A

DP Column

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Total vent height measured from the highest connected draft hood outlet or flu collar to the terminus not including rain cap to be able to reduce

A

At least 10’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

If the appliance outlet size is 12 inch or smaller how much can you reduce ?

A

One table size only

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If an appliance outlet size is large than the 12 inch how much can It reduce?

A

Two tables sizes only, engineers decisions usually at this size

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Can Appliances with draft hood, smaller than 5 inch be reduced

A

No

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

For each 90° elbow beyond to the capacity of the venting sizing table will be reduced by what for draft appliances and fan assisted appliances

A

10% for draft hood
15% fan assisted

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What length should the common vent connecter manifold not exceed per inch of diameter?

A

1.5’ per inch of diameter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Using rule of the method to determine the size of event prevent connecter for tour more appliances what information is used?

A

The size of the draft hood or flu collar outlet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Rule of thumb vent sizing for more than one APPLIANCE

A

States that the area of the vent will be equal to the area of the largest draft hood or flu collar +50% of the sum of the outlet areas of the additional appliances

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

How much do the tables reduce if the common vent is offset?

A

20%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the smallest allowable size of chimney?

A

12” square inches. Which is equal to a 4” diameter pipe

17
Q

What is the maximum capacity of a clay tile or transit liner chimney?

A

125% of appliances input