Air Supply Flashcards

1
Q

With air supplied outdoors what will happen if the opening is not large enough?

A

Incomplete combustion and result creating Aldehydes, carbon monoxide and soot

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

With air supplied from outdoors, what will happen if the opening is too large

A

Too much cold air enters in the winter, inviting someone to block off the opening

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The formula to size the air supply opening to be installed in the wall

A

1 in.² for every 1000 BTU of appliance input

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Air Supply determination what is the method of calculating the size of opening from the building into the mechanical room?

Where must this opening be?

A

One square inch for every 1000 BTU of appliance input

Located between 6 and 18 inches from floor level, which means that the maximum opening will be 12 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Location of combustion air opening if one or more of the appliances have a draft hood or barometric damper

A

There will be a second opening the same size as the one for combustion, but it will be placed high on the wall

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where must the Air Supply duct be ran?

A

This duck must be run from the outdoors and terminate within 1 foot above, and 2 feet horizontally of the appliance burner having the largest input

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When will a square duct may be used

A

If the air supply deck area is 9 in.² or larger at the smallest dimension of the duct is not less than 3 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the minimum height for an outdoor air supply opening?

A

1 foot above ground level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How is the outdoor air supply sized when install installing appliances with draft control devices?

A

The opening must be permanent and must be at or deducted to a location that is no more than 18 inches above the floor level and not less than 6 inches above floor level

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How was the air supply opening size calculated for power burners?

A

All inputs over 400,000 BTU require 1 in.² for each 30,000 BTU

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the smallest allowable dimension for a grill or screen?

A

Quarter inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

When a mechanical fan supplies, the air what has to control the gas

A

A manual reset control

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A sheet metal adjustable 90 elbow has a resistance to natural airflow equal to how many feet of straight pipe

A

10

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where should the ventilation opening be placed?

A

Near the top of the room as possible

How well did you know this?
1
Not at all
2
3
4
5
Perfectly