Hydronic Radiant Heating And Heat Loss Calculations Flashcards

1
Q

Where is a cushion/ expansion tank normally placed

A

Placed upstream of the circulator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Heat transfer by movement of fluid

A

Convection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Thin layer of reflective material placed below or above the heat transfer unit to transfer heat in the direction required

A

Radiant barrier

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

1/R = ??

A

U factor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

This heating system heats a space from the ceiling down

A

Forced air system

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What are the components of a finned baseboard system

A

Copper tube, aluminum fins , and an enclosure

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

This heating offers radiant heating that heats the objects in the space and have little effects on the air in the room

A

Radiant infloor heating

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Is the temperature of the air in a room at different levels

A

Stratification

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is installing radiant floor heating not recommended

A

Below cabinets or pantry’s that store food

Underneath refrigerators and freezers increase load on those appliances

Near water closets

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Delta T is the difference between radiant floor temperature and the temperature of surrounding colder surfaces

What is the advantage of this

A

The greater the temperature difference between the two surfaces the faster the heat transfer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is not recommended with setting the room temperature with radiant floor heating ?

A

Setting back the system at night is not recommended, due to slow response time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Most building and municipal codes require that any occupied building must have a way to exchange the air called what

A

Air exchangers

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What’s important to consider these installing snow melt systems

A

Ensure proper drainage system to prevent ice build up

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

This piping meets or exceeds any of the stringent pressure and temperature tests required by code

Ideal for radiant flooring

A

Pex

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Recommended maximum lengths for infloor heating

A

3/8” ID- 76m/250’
1/2” ID- 91m/300’
3/4” ID- 152 m/ 500’

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Tubing manufacturers also make headers, but these headers are pipe specific. Connecting one manufacturers tubing to another’s header does what?

A

Voids the warranty

17
Q

When connecting tubing to headers what must be followed

A

Joined per manufacturers specifications

18
Q

These are installed on manifolds to ensure equal flow rate to each circuit

A

Balancing valves

19
Q

When are balancing valves not required

A

Lass than 10% different between circuits

20
Q

Maximum floor temperature

A

140 Fahrenheit

21
Q

What temperature can the floor surface not exceed in areas where people stand for long periods

A

25 Celsius or 77 Fahrenheit

22
Q

What should the Floor surface temperature not exceed in a dwelling or commercial space

A

31 Celsius or 88 Fahrenheit

23
Q

What should Floor surface temperatures not exceed in bathrooms, indoor swimming pools and foyers

A
  1. Celsius or 91 Fahrenheit.
24
Q

What temperature should floor surfaces not exceed in radiant panel perimeter areas

A
  1. Celsius or 95 Fahrenheit.
25
Q

What should a radiant panel be protected with?

A

High limit temperature control valve

26
Q

What temperatures are considered low temperature systems

A

Below 140 Fahrenheit

27
Q

What temperatures are considered high temp systems

A

Over 140 Fahrenheit

28
Q

What is the calculation for U factor

A

1/R value = ufactor

29
Q

For most heat lost calculations what’s recommended with rounding of the measurements

A

To the nearest quarter of a foot

30
Q

The difference between the indoor design and the outdoor design temperature

A

Design temperature difference

31
Q

What is infiltration based on?

A

BTUH per hour per cubic foot of air within a space

32
Q

Heat is lost through the ceiling by conduction and this loss is referred to as what

A

Transmission loss

33
Q

What percent must be added to the heat loss calculation in bathrooms