These fixtures are required by the Alberta building code in every building
Water closet, bathtub, or shower, laboratories, and kitchen sinks
Garbage grinders and dishwashers must be installed with what
A trap
How much waterline should be coiled up behind a refrigerator?
Enough, so it can be pulled out from the wall without damaging the waterline
What’s an uncommon way of preventing backflow?
Gate valve may be used in the branch
What should weeping tiles be installed on?
Washed rock 1 inch
Covers in area, 12 inch horizontal and vertically around the pipe
What three items should be installed in the discharge line of a sump pump in order
Union,check valve, ball valves
With the sewage pump when explosive gases are present the vent must be terminated how
Separately through the roof, one size smaller than the largest inlet into sump
If a sump does not have an automatic automatic controls, how must it be sized?
Enough to hold 24 hours of sewage
For sump pumps, how are they typically sized?
The outlet size on the pump typically determines
How often should a sump pump be serviced?
Three times a year at least
How do you calculate the hydraulic load from a fixture that produces a continuous or semi continuous flow such as a pump or air conditioner?
31.7 fixture units for each litre per second of flow
What’s an important rule for sizing the diameter of a stack vent?
May not be less than 1/2 the size of the soil or waste stack at space