Service Water Flashcards

1
Q

System purpose?

A
  • Provides cooling water to various components in the Aux building, turbine building, containment building, and the intake structure
  • Serves as a back-up to the suction of the AFWpumps and the Isolation valve seal water tank. (IVSW)
  • Supplies water for the CircWater Pump seals and screen wash
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Power supplies for Service water Pumps?

A
  • A,B powered from E1
  • C,D powered from E2
  • D can also be powered from DS bus by the kirk key in the CCW pump room.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Kirk Keys in the plant?

A
  • CCW Pump room, SW pump to DS bus
  • Waste gas disposal panel, MCC-5 to the DS Bus
  • South Cable vault room, (MG set room) N51 to DS Bus
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

R-16 Process Monitor, location, what it monitors

A
  • Located in the Aux Hallway behind the Station air compressor.
  • Monitors the CV HVH units cooling discharge for radiation indicative of a leak from the CV atmosphere in the cooling water.
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

SW-739 and 740

location and what they do

A
  • Located in the CCW pump room south of the CCW heat exchangers.
  • 2 positions (limited to)
  • Pos1- 5000gpm for each CCW heat Xchagner.
  • Pos2-10000gpm for one CCW heat Xchanger
  • Not to cause pump runout on 2 pumps on accident conditions
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Service Water Booster Pumps (SWBP)

location and power supplies

A
  • Aux hallway
  • A powered by MCC-16
  • B powered by MCC-18
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What does the SWBP do for us?

A
  • At least one is required to supply cooling water to the CV HVH Units.
  • SI auto start with SW pump start
  • Blackout, must have 30psig
  • Pump trips with suction pressure 12psig for longer than 10 seconds
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

V-6-12 A,B,C,D power supplies

A
  • V6-12A (South Hdr Isol) MCC5
  • V6-12B (HDR cross connect) SW pump A/B side MCC-5
  • V6-12C (HDR cross connect) SW pump C/D side MCC-6
  • V6-12D (North HDR Isol) MCC-6/5 via manual transfer switch
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

V6-16 A,B,C power supplies

Turbine Building Isolations

A
  • V6-16A (North Header) MCC-9
  • V6-16B (South Header) MCC-10
  • V6-16C (Both) MCC-10/9
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Chemical Treatment (what chemical) added to the Service water? and why?

A

-Sodium Hypo-chlorate added to system to minimizing biofouling

How well did you know this?
1
Not at all
2
3
4
5
Perfectly