CCW system Flashcards
1
Q
Purpose of the system
A
- Removes heat from the plant components during power operations, plant cooldown, plant shutdown, and during postulated post-accident conditions.
- Provides cooling to the RCP motors and thermal barrier heat exchangers.
- Provides cooling to safety-related equipment.
2
Q
CCW pump power supplies?
locations?
A
-A-480V DS Bus (Not tech spec b/c of DS) -B-E-1 -C-E-2 -CCW pump room
3
Q
CCW pumps start on what PSI?
A
-auto-start on 78psig
4
Q
CCW Surge Tank Vent
RCV-609 & CC-707
A
- RCV-609 is gaggged open to prevent over pressurization of the CCW system.
- CC-707 serves as secondary relief
- Relief valves sized to relieve maximum flowrate following rupture of the RCP thermal barrier cooling coil
5
Q
CCW Pump A powered from? Can be controlled by?
A
- DS Bus
- DS panel in the Charging pump room