RQC-KNOW (Brandy) Flashcards
What are the Rx Trip signals associated with NIs?
- SR High Flux
- IR High Flux
- PR High Flux, Low Setpoint
- PR High Flux, High Setpoint
- PR High Positive Rate
- Overtemp delta T
- Overpower delta T
What is the
Setpoint
Coincidence
Interlock associated with the SR High Flux Rx Trip?
90,000 cps and rising on 1/2
P-6
What is the Setpoint Coincidence Interlock associated with the IR High Flux Rx Trip?
22.5% (20%) RTP and rising on 1/2
P-10
What is the Setpoint Coincidence Interlock associated with the PR High Flux, Low Setpoint Rx Trip?
20% RTP and rising on 2/4
P-10
What is the Setpoint Coincidence Interlock associated with the PR High Flux, High Setpoint Rx Trip?
107% RTP and rising on 2/4
What is the Setpoint Coincidence Interlock associated with the PR High Positive Rate Rx Trip?
4.5% and rising in 2 secs on 2/4
What is the Setpoint Coincidence Interlock associated with the Overtemp delta T Rx Trip?
Variable setpoint as displayed on control board meter
2/4
What is the Setpoint Coincidence Interlock associated with the Overpower delta T Rx Trip?
Variable setpoint as displayed on control board meter
2/4
What are all the Rx Trip Signals?
SR High Flux IR High Flux PR High Flux, Low Setpoint PR High Flux, High Setpoint PR High Positive Rate Overtemp Delta T Overpower Delta T Pressurizer Pressure, High Pressurizer Pressure, Low Pressurizer Water Level High RCS Loss of Flow UV- RCP Busses Underfrequency - RCP Busses RCP Breaker Position SG Water Level, Low-Low SG Water Level Low w Feed Flow < Steam Flow Any SI Signal Turbine Trip Manual
What is the Setpoint Coincidence Interlock associated with the Pressurizer Pressure High Rx Trip?
2385 # and rising on 2/4
What is the Setpoint Coincidence Interlock associated with the Pressurizer Pressure Low Rx Trip?
1950# and lowering on 2/4
P-7
What is the Setpoint Coincidence Interlock associated with the Pressurizer Water Level High Rx Trip?
92% and rising on 2/3
P-7
What is the Setpoint Coincidence Interlock associated with the RCS Loss of Flow Rx Trip?
91% and lowering
> P-8 2/3 on 1/4 Loops
< P-8 > P-7 2/3 on 2/4 Loops
What is the Setpoint Coincidence Interlock associated with the UV- RCP Busses Rx Trip?
88 Volts indicated and lowering on 1/2 on 2/4 busses
P-7
What is the Setpoint Coincidence Interlock associated with the Underfrequency - RCP Busses Rx Trip?
58.2 Hz and lowering on 1/2 on 2/4 busses
P-7
What is the Setpoint Coincidence Interlock associated with the RCP Breaker Position Rx Trip?
Open auxiliary switch on 2/4
P-7
What is the Setpoint Coincidence Interlock associated with the SG Water Level Low-Low Rx Trip?
5% (22%) and lowering on 2/3 on 1/4 SGs
What is the Setpoint Coincidence Interlock associated with the SG Water Level Low w Feed Flow < Steam Flow Rx Trip?
15% (26%) and lowering on 1/2 on 1/4 SG
AND
0.71E6 (1.47E6) lb/hr on 1/2 on same SG
What is the Setpoint Coincidence Interlock associated with the SI Signal Rx Trip?
Either Train
What is the Setpoint Coincidence Interlock associated with the Turbine Trip Rx Trip?
Auto Stop Oil Pressure 800# and lowering on 2/3
OR
Stop Valves 1% and lowering on 4/4
C-8
What is the Setpoint Coincidence Interlock associated with the Manual Rx Trip?
Manual Switches 1/2