MFP Turbine Ctrls Flashcards
1
Q
When are the MFPs forced to speed ctrl?
A
- Both MS Press xmitters Fail
- Both MFP Hdr # xmitters Fail
- MFP DP Setpoint xmitter Fails
- Other MFP Trip when > 60% Power
- MFP Speed > 5220 (5300) rpm when its forced to speed ctrl
2
Q
What will override MFP Speed Ctrl on U2?
A
- MFP 1st Stage # Limiter
- Will close down on control valves to prevent excessive 1st stage #. (@ 105# first stage # and 5300 rpm)
3
Q
When is MFP ΔP enabled?
A
- MFP Speed > 3500 rpm
4
Q
What are the Hardwired MFP trips?
A
- Manual
- Rx Trip
- SI
- Hi Hi SG Lvl (P14)
- IOPS 110% 5740(5830) rpm
- Thrust Bearing Wear
5
Q
What are the DCS MFP trips?
A
- Condenser Vacuum Low < 20”(15”) Hg
- Overspeed 107% 5585(5670) rpm
- Loss of suction pressure < 180# for 5 sec
- Lube Oil Pressure Low < 4#(13#) for 5 sec
- Low trip header pressure 800 psi
6
Q
When does the Main Steam to the MFP Automatically open for fast action Main Steam Supply to MFPs in U2
A
- When MFP steam control valves > 65% open, MS supplies open until control valves < 63%
- When MFP trips, MS to running MFP set to 105#
- Minor perturbation
7
Q
What feeds the Steam Flow input for the ΔP Control for program ΔP?
A
- Total Steam Flow selected Channel
- No Load Set point
8
Q
What transmitters feed the ΔP Control for actual ΔP?
A
- UPC-102A/B (Bypass Steam header) (Higher of 2)
- FPC-250A/B (6A FW Htr outlet) (Lower of 2)
9
Q
What happens when a MFP is forced to speed ctrl?
A
- Remaining MFP shifts to SPEED CONTROL
- SPEED TARGET set to Max (5220/5300) RPM
- RAMP RATE is calculated to bring speed reference to Max in 20 seconds.
- U2: ARV-11/12 setpoint ramped to 105#
10
Q
What parameter tells the MFP that power is > 60%?
A
- dP setpoint > 110 (U1)/116 (U2) psid