MFP Turbine Ctrls Flashcards

1
Q

When are the MFPs forced to speed ctrl?

A
  • Both MS Press xmitters Fail
  • Both MFP Hdr # xmitters Fail
  • MFP DP Setpoint xmitter Fails
  • Other MFP Trip when > 60% Power
  • MFP Speed > 5220 (5300) rpm when its forced to speed ctrl
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will override MFP Speed Ctrl on U2?

A
  • MFP 1st Stage # Limiter

- Will close down on control valves to prevent excessive 1st stage #. (@ 105# first stage # and 5300 rpm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

When is MFP ΔP enabled?

A
  • MFP Speed > 3500 rpm
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the Hardwired MFP trips?

A
  • Manual
  • Rx Trip
  • SI
  • Hi Hi SG Lvl (P14)
  • IOPS 110% 5740(5830) rpm
  • Thrust Bearing Wear
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the DCS MFP trips?

A
  • Condenser Vacuum Low < 20”(15”) Hg
  • Overspeed 107% 5585(5670) rpm
  • Loss of suction pressure < 180# for 5 sec
  • Lube Oil Pressure Low < 4#(13#) for 5 sec
  • Low trip header pressure 800 psi
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When does the Main Steam to the MFP Automatically open for fast action Main Steam Supply to MFPs in U2

A
  • When MFP steam control valves > 65% open, MS supplies open until control valves < 63%
  • When MFP trips, MS to running MFP set to 105#
  • Minor perturbation
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What feeds the Steam Flow input for the ΔP Control for program ΔP?

A
  • Total Steam Flow selected Channel

- No Load Set point

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What transmitters feed the ΔP Control for actual ΔP?

A
  • UPC-102A/B (Bypass Steam header) (Higher of 2)

- FPC-250A/B (6A FW Htr outlet) (Lower of 2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What happens when a MFP is forced to speed ctrl?

A
  • Remaining MFP shifts to SPEED CONTROL
  • SPEED TARGET set to Max (5220/5300) RPM
  • RAMP RATE is calculated to bring speed reference to Max in 20 seconds.
  • U2: ARV-11/12 setpoint ramped to 105#
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What parameter tells the MFP that power is > 60%?

A
  • dP setpoint > 110 (U1)/116 (U2) psid
How well did you know this?
1
Not at all
2
3
4
5
Perfectly