Ctrl Room Ventilation Flashcards
What is the purpose of the Ctrl Rm Ventilation?
- Maintain control room below 120°F during 4 hour coping period of Station Blackout
- Maintain normal temp less than 85°F
- Keep CR pressurized
- Maintain acceptable smoke levels in CR
- Keep temperature in CR less than 97 deg F during accident
- Remove iodine and particulate
- Maintain rad levels during DBA less than 5 Rem
- Isolate CR during toxic gas release
How does ESW interface with the CRAC?
- Cooling water for condensers
- Backup supply for cooling coils
When is the backup cooling capability lost with respect to ESW to the cooling coils?
- Backup capability lost if ESW > 65°F
What are the CR Pressurization Fan starts?
- SI in either Unit (Train Spec)
- CR High Rad (unit specific)
- CRCV Fire (CO2 or Halon actuation)
- Manual
What the trips of the CRAC chiller package?
- Load Con**
- High Discharge Pressure
- Low Suction Pressure
- Low Temperature
- Low Oil Pressure
- Overload
How do VRV-315/325 fail on a loss of air?
- Fail open with full flow to chillers
(ACRDA are motor operated and fail as is on loss of pwr)**
Describe a design function of the Control Room Ventilation System?
- Maintains control room habitable for 30 days post accident while maintaining dose less than 5 rem TEDE to satisfy 10 CFR 50.36
If U-1 gets a CRCV Fire signal and All U-1 CR Vent Sys Auto actions occur as expected
THEN
U-1 gets a CR High Rad signal,
Does U-1 CR vent Sys realign?
- No, “First in Wins.” The U-1 CR Vent System stays aligned for the U-1 CRCV Fire signal
When will HV-ACR-DA-2A Clean Up Intake Damper
HV-ACR-DA-2A go to part open?
-If HV-ACR-DA-2 isn’t in part open after 45 sec since actuation
What does TS 3.3.7 B (CREV system Actuation Instrumentation) State?
- If One or more required functions with two trains inoperable
IMMEDIATELY: - Place one CREV train in pressurization/cleanup mode
AND - Enter applicable Conditions and Required Actions for 1 CREV train made Inoperable by Inoperable CREV actuation instrumentation
OR - Place both CREV trains in pressurization/cleanup mode
What does TS 3.7.10 B (CREV system) State?
- If 1 or more CREV trains Inoperable due to CRE Boundary in Modes 1-4
IMMEDIATELY: - Initiate action to implement mitigating actions
What does TS 3.7.10 F (CREV system) State?
- If 2 CREV trains inoperable during movement of irradiated fuel assemblies
OR - 1 or more CREV trains inoperable due to an inoperable CRE boundary during movement of irradiated fuel assemblies
IMMEDIATELY: - Suspend movement of irradiated fuel assemblies
What does TS 3.7.10 G (CREV system) State?
If 2 CREV trains inoperable in Modes 1,2,3,4 for reason other than B (CRE Boundary) and C (filter)
IMMEDIATELY:
- Enter LCO 3.0.3
What does TS 3.7.11 D (CRAC system) State?
- If 2 CRAC trains Inoperable during movement of irradiated fuel assemblies
IMMEDIAELY: - Suspend movement of irradiated fuel assemblies
What does TS 3.7.11 E (CRAC system) State?
If 2 CRAC trains inoperable
IMMEDIATELY:
- Enter LCO 3.0.3