Roof (Thickness) Flashcards

1
Q

Roof plates corroded to an average thickness of ,,,,,,,,, shall be repaired or replaced

A

< 0.09” in any 100 in.2 area or

roof plates with any holes through the roof plate

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Supported Cone Roofs -

The minimum thickness of new roof plates shall be ,,,,,,

A

3/16 “ (4.76 mm) plus C.A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Self-supporting Roofs-

The nominal thickness of new roof plate shall be,,,,

A

3/16 “ (4.76 mm) or

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Plates more than 40 mm (1.5 in.) thick shall be of

A

killed steel made to
fine-grain practice and
Heat treated
Impact tested

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Plates less than or equal to 40 mm (1.5 in.) thick may be used ,,,,,

A

at or above the DMT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The minimum thickness of new roof plates shall be ,,

A

3/16 “ (4.76 mm) + C.A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly