Pump Charts Flashcards
You are supplying a Blitzfire @ 1900 litres per minute and a 65mm hand line @ 510 kPa. Your static hydrant pressure was 450 kPa. The compound gauge now reads 360kPa.
Can you supply an aerial with an Akromatic 1250 nozzle?
No
What pressure is added for a highrise system when calculating pump discharge pressure?
150 kpa
You are flowing 700 litres/minute with a 44mm hand line through five 15m lengths of 44mm hose. What is your pump discharge pressure?
1100 kpa
What is the friction loss per length of a 65mm hose flowing 1400 litres per minute?
80 kpa
What is the pump discharge pressure for a highrise fire on the 36th floor?
2340 kpa
You are supplying two 44mm hand lines at 950ka and an aerial with an Akromatic 1250 nozzle. You are being supplied by a hydrant with a static pressure of 450 kPa through 3 lengths of 125mm hose. According to table 2.3 how much remaining water is available?
130 lpm
What is the optimum nozzle pressure for solid bore hand lines?
350 kpa
You are supplying a Blitzfire set on “low” flowing 1900 lites/minute through six-15m lengths of 65mm hose.
What is the nozzle pressure?
970 kpa
You are supplying a Blitzfire with a 32mm stackable tip @ 960 kPa on a leader line and a 44mm jumpline @650 kPa.
Your compound gauge has gone from 550 ka down to 478 kPa. How much water is available according to chart
2.4?
4600 lpm
What is the coefficient of friction for a 77mm hose?
.4