Private sewage Disposal System Flashcards
a septic tank into the subsurface disposal field, or seepage pits
PRIVATE SEWAGE DISPOSAL
a watertight receptacle which receives discharge of a sanitary plumbing system
SEPTIC TANK
a loosely lined excavation in the ground which receives the discharge of a septic tank
SEEPAGE PIT
a non-watertight lined excavation in the ground which receives the discharge of a sanitary drainage system or part there of
CESSPOOL
a cesspool that is not watertight
LEECHING CESSPOOL
an outhouse or structure used for the deposition of excrement
PRIVY
a pit beneath a privy where excrement collects
PRIVY VAULT
_______ are conducted to determine the absorption qualities of questionable soils
PERCOLATION TEST
What are the basis of DENR in approving if the bldg sewer may be connected to private sewage disposal system?
Location
Soil porosity
Ground water level
(LSG)
PD 856
SANITATION CODE OF THE PHILIPPINES
Septic tanks design shall produce a _________
clarified effluent
What is the minimum compartments of septic tank?
2
what is the recommended minimum compartment of septic tanks by LGU’s?
3
What is the liquid depth of septic tanks?
0.6 m-1.8m
What is the minimum inlet compartment of a septic tank?
2/3 of the septic tank
What is the minimum capacity of the first compartment of a septic tank?
2 cu.m
What is the minimum width of a septic tank?
0.90 m
What is the minimum length of the first compartment of a septic tank?
1.5m
What is the maximum outlet compartment of a septic tank?
1/3 of the septic tank
What is the minimum capacity of the secondary compartment of septic tank?
2 cu.m
What is the minimum length of the secondary compartment if septic tank has over 6 cu.m capacity?
1.5 m
What is the minimum size of the inlet and outlet pipe for septic tank?
Same as the size of connecting sewer pipe
What is the minimum number of manholes of a septic tank?
2
What is the minimum dimension of a manhole?
508 mm
How many manholes are over the inlet compartment?
1 manhole
How many manholes are over the outlet compartment?
1
Add 1 more manhole above the baffle wall if the first compartment exceeds _____ in length
3.7 m
What is the vertical clearance of inlet invert pipe above outlet invert pipe for septic tank?
50.8 mm (2”)
What is the vertical clearance of the cover of the septic tank above the back vent opening?
50.88 mm (2”)
How much is the extension of inlet and outlet pipe or baffle partitions between compartments above the water surface?
101.6 mm (4”)
What is the minimum vertical leg of the inlet and outlet fitting?
104.6 mm (4.1”)
What is the minimum inverted fitting installed in the inlet compartment side of the baffle??
104.6 mm (4.1”)
What is the minimum horizontal dimension of the baffle type fitting measured at the inlet and outlet pipe inverts?
106.6 mm (4.2”)
How much is the extension of side walls above the liquid depth?
228.6 (9”)
How much is the extension of the inlet and outlet pipe or baffle below the water surface?
304.8 mm (12”)
What is the minimum earth load support of septic tank cover when the maximum coverage does not exceed 9 m?
14.4 kpa
What is the minimum bituminous coating extension below the water line for concrete septic tanks and shall cover all of the internal areas above that point?
101.6 mm (4”)
What is the minimum wall thickness of any steel septic tank?
Gauge 12 US (2.8mm)
What are prohibited septic tanks and baffles?
Wooden septic tanks and baffles
what is the minimum area of trench bottom for disposal fields?
14 sqm
what is the sidewall area of disposal fields that may be added to the trench bottom?
304.8 mm to 914.4 mm
What is the maximum depth of excavation within a water table for a leach line or leach bed?
1.5 m
what is the raking depth of trenches before placing filter materials on drain lines, to remove compacted surfaces?
25.4mm (1”)
what is the *size of clean stone, gravel, slag, or similar filter material for a disposal field?
19.1 mm to 63.5 mm (3/4” to 2 1/2”)
What are approved filter materials put above the drain pipe to prevent closure of voids with earth backfill?
Untreated building paper, Straw, similar porous material
What is staked in the trench to the depth of the filter material as support for drain tile or flexible pipe which will maintain alignment?
GRADE BOARD
How much is the termination of filter material when seepage pits are used in combination with disposal fields?
1.5 m
What is needed for two or more drain lines to receive lateral lines?
DISTRIBUTION BOX
what is required if quantity of sewage exceeds 152.4 linear meter?
DOSING TANK
What is the interval of discharge of dosing tank via automatic siphon pump?
3 hrs or 4 hrs
What is the dosing capacity of a dosing tank at one time?
60% to 75%
How many siphons or pumps required if total length of pipe exceeds 304.8 m, each serving 1/2 of the reaching field?
2 siphons or pumps
What is the minimum number of drain lines per disposal field?
1
What is the maximum length of each line of the disposal field?
30.5 mm
what is the minimum bottom width of trench for disposal field?
457.2 mm
What is the maximum bottom width of trench for disposal field?
914.4 mm
What minimum spacing of distribution lines of disposal fields, center-to-center?
1.8m
What is the minimum depth cover of line of disposal field?
304.8mm