Oily Waste and Non-Rad Waste System Flashcards
Where does the Yard Area Sump normally pump to? A. Circ Water Intake Structure B. OW Separator C. Retention Tanks D. LRS TDS Tanks
A. Circ Water Intake Structure
Flow orifices are installed on the discharge of all OW sump pumps EXCEPT: A. Yard Area B. OW Sump C. North Condenser Sump D. Diesel Generator Sumps
D. Diesel Generator Sumps
What sump pumps are supplied with Demineralized Water (DW) for bearing lubrication? A. Diesel Generator sump pumps B. Turbine Building sump pumps C. Control Building sump pumps D. Yard Area sump pumps
C. Control Building sump pumps
What sump pumps are supplied with Domestic Service Water (DS) for bearing lubrication? A. Diesel Generator sump pumps B. Turbine Building sump pumps C. Control Building sump pumps D. Yard Area sump pumps
A. Diesel Generator sump pumps
The Control Room receives a hi-hi level alarm for the OW Sump. The AO responds immediately to investigate the alarm. Assuming normal operation, the AO reports ________ pump(s) are running.
A. No
B. Both
C. One
B. Both
What protects a sump pump on a low sump level? A. Lo level switch B. Lo-lo level switch C. Alternator D. Overcurrent Circuit
B. Lo-Lo level switch
The following are discharge paths for sumps in the turbine building EXCEPT: A. TDS tanks B. Chemical Drain Tanks C. Chemical Waste Neutralizing Tanks D. OW Sump
B. Chemical Drain Tanks
There is a water line break in the Non-Class Battery room. The water from the room flows into the acid neutralizing sump. What is the next location in the flowpath? A. South Condenser sump B. North Condenser sump C. Turbine Building sump D. OW Sump
B. North Condenser sump
Where do the CST pump house drains go? A. North Condenser sump B. Turbine Building sump C. South Condenser sump D. Yard Area sump
A. North Condenser sump
All of the following ultimately end up in the West Control Building sump EXCEPT:
A. “A” train battery room
B. “B” train battery room
C. Essential Cooling Water Heat Exchanger Tube Side Drains
D. “A” class switch gear room
B. “B” train battery room
The Yard Area sump can receive drains from all of the following EXCEPT:
A. Demineralized Water Storage tank overflow
B. Auxiliary Boiler and Generator area
C. Turbine Building roof drains
D. CST pump house drains.
D. CST pump house drains