Exam 5 prep Flashcards
MG and Excitation, Cond and Cond Transfer, GS, AR and Isophase and Stator cooling
Which of the following supplies cooling to the generator collector housing?
A: WC
B. TC
C: It is air cooled via its own AHU
D: PW
A: WC
State the Main Generator ratings and where the armature windings and field windings are located.
What is the purpose of the collector rings?
- Main Generator outputs 24kV
- 22.8kV-25.2kV terminal voltage band
- 560 MVAR (boost) to 310 MVAR (buck)
- Stepped down through the Aux Transformer to 13.8kV
- Stepped up through the Main Transformers to 525kV
- Armature windings on the stator, Field windings on the rotor
- Collector Rings take the DC from excitation and transfers it to the rotor via brushes
Why is the generator pressurized with H2 gas to 75 psig?
What is the normal purity and H2 temperatures within the generator?
Removes heat from windings, stator and generator dome. Cooled by TC via 4 H2 coolers. Normal purity is >90%. H2 gas temperatures are kept between 48C and 30C.
What is the purpose of the Generator core monitor?
monitors H2 gas for insulation breakdown (pyrolysates)
How is the GCM aligned?
The pyrolysate filter is normally bypassed.
What is the GCM monitoring and what is a normal reading?
State when the pyrolysate collector filter is placed in service and what it is detecting.
- Normally 90% current flow, when it goes down to 75% or less it actuates an alarm, @ 60% a 2nd alarm comes in.
- After 5 continuous seconds overheating validation cycle automatically initiates
- Filter is then placed in service, if Ion Chamber current goes >/= 75% the event has been validated. If not then a malfunction alarm is now in.
- Once validated the pyrolysate colector collects sample of the particulate
What are the Main Xfmr amp limits with respect to isophase cooling?
- With cooling:
- Main Transformer bus rating: 40,000amp
- No cooling ratings
- For 30 min you can maintain rated amperage
- Aux Transformer: 4000 amp limit
- Main Transformer: 23,000 amp limit
How is cooling supplied to the MAIN XFMR?
What happens on a MXFMR trip?
- Upon Excitation 1st bank starts, @ 70C winding temp 2nd bank starts, @ 75C winding temp 3rd bank starts
- This is both the oil pump and the cooling fans for the associated bank
- If cooling is lost to the main transformer then 30 minutes to restore if it cannot be restored then Generator must be tripped
- All pumps/fans trip on MT trip due to electric stratification (caused by excessive circ of cold oil)
How is cooling supplied to the UAT?
If Winding/Oil Temp > 80C, what actions should be taken?
- Natural Circ Oil and Forced Air
- If temperature exceeds 80C then the transformer must be de-energized immediately (generator trip)
What is the purpose of the generator bkr sync check?
- Prevents closing in the Generator output breaker unless within 10 degrees from top center.
How is the second generator beraker closed when paralleling the generator on to the grid?
MUST USE THE SYNCH BYPASS TO CLOSE IN THE SECOND GENERATOR OUTPUT BREAKER
Will the Rx trip on a UAT fault at 100% power?
No. The turbine will trip and NAN-S01 and 2 will FBT to NAN-S03 and 4, but the Rx will not trip.
Describe a simultaneous trip and what will happen to the unit.
Simultaneous Trip = direct trip of MG(also UAT lockout) (it trips first) = highest MG protection
- Excitation TRIP
- Turbine TRIP
- Unit Auxiliary Transformer supply breakers to NANS01 and NANS02 TRIP
- Fast Bus Transfer of NANS01 and NANS02
- TRIP and block re-closure of 525KV Generator Breakers
Describe a sequential trip and what happens to the unit.
Sequential Trip = auto actions in order to prevent MG from motoring when the turbine trips first. Gen trips on reverse power
- Trip and block re-closure of 525KV Generator Breakers
- Unit Auxiliary Transformer supply breakers to NAN-S01 and S02 TRIP
- Fast Bus Transfer of NANS01 and NANS02
- Excitation TRIP
Describe a coastdown trip and what happens to the unit.
-
Coastdown trip (used to maintain voltage from the output of the generator to the RCP motors)
-
MUST meet the following conditions
- Turbine Trip
- Reverse Power condition
- Loss of power on NANS03 and/or NANS04
- Reactor Trip
- When these conditions are met then:
- Load shed all breakers on NANS01 and NANS02 except those that supply the RCPs
- Trip and block re-closure of 525KV Generator Breakers
- Initiate the MN GEN COAST DOWN TRIP annunciator
- 20 second timer times out or NANS01 or NANS02 voltage reaches 80% then the following:
- Trip Unit Auxiliary Transformer supply breakers to NANS01 and NANS02
- Trip RCP breakers
- Trip the Main Generator Exciter
-
MUST meet the following conditions
State the Main generator and transformer trips.
- Backup distance relay
- Reverse Power (inoperable if not connected to the grid) (backup 30 sec later)
- Loss of Field
- Negative Sequence
Startup/Shutdown
- S/U OC
- Stator grounds
- UF
- Differential
- Volts/Hz
- Potential unbalance
UAT:
- OC
- Ground
- Differntial
MT
- Ground
What will cause the hotwell drawoff valve to fail closed?
- Loss of IA
- Feed Pump low suction pressure
- High cation conductivity in hotwells
What is used to rapidly slow the trubine?
How are they operated?
In what position will it fail?
- Vacuum breakers on each shell allow rapid lowering of turbine speed
- Spring shut & air opened. This means they fail closed on loss of air
- Controlled from single handswitch on B07.
- Indication will be dual unless all 3 are in the same position
What will happen if a LPFW heater experiences a HI HI condition?
- HI-HI Level in any heater will cause its associated string to automatically close its associated inlet and outlet valves
Why is MFWPT lube oil system started before starting the first Cond pump?
Start MFP lube oil system before starting cond pp because MFP may rotate/damage brgs (alarm if you do)
How are the B Cond pump mini flow and lo lo level trips aligned when the B cond pump is aligned to one hotwell or the other?
The suction MOV switch aligns B Cond pump miniflow valves based on which one or both suctions are opened. It also aligns the LO LO lvl trip to the appropriate hotwell section.
State the Cond pump trips.
Trips:
- Low Flow (< 3600 gpm for 45 sec)
- B pump must have one suction valve full open
- 30” in hotwell half (lo-lo level); (B - 30” on either hotwell aligned to)
In what position does the cond pump miniflow fail?
-
FAIL OPEN on loss of air or power
- “A” and “C” powered from NNN –D12
- “B” NNN-D11 (both)
Regarding the Condensate polishing demins:
How does CDV-195 operate to bypass around the demins?
What will cause the bypass to open?
- CDV-195 provides a bypass around the demins in case flow gets blocked or demins are not in service
- Reverse acting controller
- Controller normally in Manual
-
Interlocks (regardless if in Manual or Auto)
- Condensate demin High D/P (>55 psid)
- IA header pressure low
- Condensate polishing skid inlet or outlet valve not fully open
Why is hotwell level maintained at 41”?
to accomodate a HDP trip at normal power. If this occurs hotwell level would drop approx 9”. Keeping HW level at 41” means that even during a HDP trip there is no danger of dropping below the 30” LO LO Cond pump trip.
How is excitation added to the generator?
On VR signal, excitation is added by the SCRs. They are forward biased SCR’s that when fired ON, raise field excitation. Full on firing = Full field strength.
State the MVAR limits associated with the main generator, to include H2 pressures and purity.
- MVAR limits – 560 boost, 310 buck
- H2 pressure limits = 30 to 75 psig (30 psig is for adequate density for cooling)
- Min H2 purity = 90% (explosion)
What is double sequencing with regards to ESFAS and what auto action prevents it from occurring?
Double Sequence – SIAS with degraded grid causes LOP and another load shed – time for HPSI pp to inject
Trips WRF bkrs
What is the PCR and how is it cooled?
Power conversion room.
- PCR HVAC
- 3 Units in a Lead/Lag formation
- If 1st unit can’t maintain temp then the system will alarm and auto start a 2nd unit
- PCR HVAC Units shutting down
- Will lead to Exciter shutdown on high temperature within several minutes.
- 3 Units in a Lead/Lag formation
What method of fire protection exists in the PCR?
- MUST BE MANUALLY ACTUATED by pulling BOTH manually operated pull handswitches
- One each next to the access stairs outside both of the normal entry/exit doors on the East side of the PCR.
- On actuation it auto shutdowns the HVAC units which will lead to room high temp shutdown
- Fire detection is stand alone and will alarm on B06 EXCTN PCR/PPT TRBL
What are the PPT’s?
-
PPT’s (Power Potential Transformers)
- 3 separate step down transformers with power taken directly from the generator terminals (via a tap in to the isophase bus upstream of the Unit Aux Transformer)
- Steps 24kV down to 1.2 kV this then goes to the exciter bridges
What are the SCRs power bridges and how many are needed for operation?
-
4 power bridges
- Only 3 needed for operation though normally 4 are in service
- Bridges basically take the 1.2kV and convert it to the appropriate amount of DC Voltage for maintaining Generator Output
How are the SCR bridges cooled?
- Each bridge has 2 cooling fans totally automated such that no matter malfunction it attempts to at least have one fan running
- Norm (L25)
- Alt (L08)
- Utilizes a power seeking ABT
- If both fans are not running then it removes the associated bridge from service (Only need 3 of 4 so this doesn’t trip excitation)
How many AC line filter cabinet fans are required and how many are normally running?
What happens if both are lost?
- Large amount of heat load from the AC Line Filters and has two of its own cooling fans. Both are always running when the generator is excited only one needed
- If you lose both: Initiates an exciter trip
What will operate the Generator Field Breaker?
-
Trips open
- Any turbine Trip
- Any generator Trip
- Any Exciter Trip
-
Closes
- When called by field flashing