N43 - Primary Water Flashcards

1
Q

Why should a leakage pump always be running?

A

to maintain level in the standpipe

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What happens if no leakage pumps are running?

A

primary water will overflow to radwaste

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

what will cause standby leakage water to auto start?

A

low discharge on running pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

what’s the purpose of the hydrogen blanket in the primary water tank?

A

limit air into the system to prevent corrosion

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

when will TG standstill pump auto-start and stop?

A

Switch in auto: starts at 62 psig primary water system pressure after turbine trip.
Stops at 62 psig on turbine roll up
(equivalent to 800 rpm)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

How long will TG standstill pump run in test?

A

10 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the power supplies to the leakage water pumps?

A

A - 13B22

B - 16B42

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

At what level does the leakage water overflow to radwaste?

A

19 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What level is the leakage water standpipe maintained at?

A

10 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What temp should primary water be entering ion exchanger and why?

A

50 deg C (122 F) to prevent damaging the resin and ions being released instead of captured

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

what’s the purpose of Primary water?

A

Cools the main generator stator, rotor, and 3 busing circuits

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What temp is the primary water maintained at compared to hydrogen? Why?

A

2 deg F higher than hydrogen gas temp to avoid gas dew point condensation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What cools the primary water coolers

A

TBCW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When will high conductivity alarm come in for each location?

A

Deionizer high 2.2 mmho/cm2

main flow 2.2 mmho/cm2

Leakage water 2.5 mmho/cm2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the power supply of the main primary water supply pump?

A

Shaft driven off turbine

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What’s the purpose of the primary water storage tank?

A

NPSH, expansion, large volume for degassing

17
Q

what pressure of the hydrogen blanket in the primary water tank

A

2-5 psig (< 1.5 psig or > 5 psig gives alarm)

18
Q

What are the primary water trips?

A

Low Rotor flow 460 gpm for 10 sec

Low Stator flow 542 gpm for 5 sec

Low busing flow (a,b,c) 25.5 gpm for 10 sec

High terminal box level 2”

PW tank level low < 78”

High stator inlet temp 60 deg F

High PW connection 20 mils (manual trip)

Add on here which ones are speed dependent