Circ Water Flashcards

1
Q

What are the circ water pump permissives?

A

HP outlet F011A/B full open

Lube water > 10 gpm

Discharge F002A/B full closed

Lock-out reset

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the circ water pump trips?

A

Motor protection

6.9kv undervoltage

Discharge valve full closed (bypassed for 30 seconds after pump start)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the purpose of circ water?

A

removes heat from main condenser

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What’s the purpose of lube water?

A

lubes shaft bearings

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What’s the primary and backup suction sources to lube water?

A

Primary - pump discharge

backup - PSW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What happens when high cooling tower basin level occurs?

A

F502 opens to divert water to plant discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What happens when F502 opens or closes?

A

opens (diverts to plant discharge basin)

close (diverts to circ water pit)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What effect does opening/closing F512 have on PSW pressure?

A

Open: discharge pressure goes down

close: discharge pressure goes up

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What valves are the blowdown valves?

A

F513A/B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What’s the primary supply for circ water pump motor thrust bearing cooling?

A

PCW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What’s the backup supply for circ water pump motor thrust bearing cooling?

A

backup pump discharge

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What occurs when stop push button is depressed to secure pump?

A

Discharge valve closes then pump trips

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What will happen if pumps are run in single pump dual train with ACT valved in?

A

Risk of pump run-out

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What’s the power supplies to the ACTs?

A

19UD from BOP 14

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What needs to be monitored while securing ACTs while plant is at power?

A

Condenser vacuum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What pressure and flow will Lube water alarm the control room?

A

< 70 psig or

< 13 gpm