N4151 - Main Generator Flashcards
What speed must the turbine be at to close the field breaker?
> 1710 rpm
what is main generator rated for?
1600 MVA
1440 MWE
697.4 MVAR
Power factor of .9
Which hydrogen cooler is temperature sensed from to control TBCW flow to hydrogen coolers?
C hydrogen cooler
What will valving out the C hydrogen cooler cause?
Loss of temperature control to the hydrogen coolers
At what RPM will the generator become de-excited?
1710 rpm
what cools the hydrogen gas for the generator?
TBCW
What cools the rotor windings, stator windings, phase connectors, and terminal bearings?
Primary Water
How is heat removed from the generator core?
Spacer segments provide radial passage for hydrogen gas flow
What circulates hydrogen gas through the generator, and where are they located?
2 Axial fans located near ends of the rotor in the rotor retaining ring