Module 6.1 Knowledge Questions Flashcards
The let by test is carried out at a pressure of…
a) 10 inches water gauge
b) 10 bar
c) 10 pascals
d) 10 millibar
d) 10 millibar
The gas/air mixture being purged from a domestic installation needs to be lit when the installation volume exceeds….
a) 0.01m3
b) 0.35m3
c) 0.071ft3
d) 0.02m3
d) 0.02m3
The maximum permissible tightness test pressure loss for a U6 meter fitted to an existing installation with max 28mm pipework and appliances connected is….
a) 1 mbar
b) 2.5 mbar
c) 4 mbar
d) 8 mbar
c) 4 mbar
After a successful let-by test the pressure should be slowly raised to….
a) 10 mbar
b) 20 mbar
c) 21 mbar
d) 23 mbar
b) 20 mbar
When designing a gas installation the maximum allowable pressure drop between the meter and any appliance is…
a) 5 mbar
b) 2 mbar
c) 1 mbar
d) 1 bar
c) 1 mbar
The IGE publication covering tightness testing of gas installations with pipework limited up to 35mm copper or DN32 steel; a volume not exceeding 0.035m3 and with a maximum rating of 16m3/hr is…
a) IGE/UP/7
b) IGE/UP/8
c) IGE/UP/1A
d) IGE/UP/1B
d) IGE/UP/1B
The gas meter that has a badged capacity of 0.035 ft3 is…
a) E6
b) U6
c) U16
d) G10
b) U6
The installation volume (IV) of a system fitted with a U6 gas meter, 10m of 35mm copper, 5m of 22mm copper pipework and a further 5m of 15mm copper would be…
a) 0.04997m3
b) 0.03252m3
c) 0.02684m3
d) 0.01977m3
d) 0.01977m3
The Purge Volume of an installation fitted with a U6 gas meter, 10m of 35mm copper, 5m of 22mm copper and a further 5m of 15mm copper is….
a) 0.04987m3
b) 0.027655m3
c) 0.03684m3
d) 0.01477m3
b) 0.027655m3
After a successful tightness test a smell of gas persists. The correct action would be…..
a) To repeat the tightness test over 5 minutes
b) To contact CORGI
c) To contact the ESP
d) To do nothing as the installation is OK
c) To contact the ESP
What is the time period that must be allowed for a domestic tightness test?
a 1 minute.
b 2 minutes.
c 3 minutes.
d 4 minutes.
b 2 minutes.
Prior to the domestic tightness test, 1 minute is allowed to check for the meter control passing gas. It this test was not carried out, the consequences could be:
a Gas may be escaping through the inlet supply.
b The gas pressure could rise within the meter.
c Gas that is escaping could be replaced from the supply.
d Gas escaping from the service would be recorded.
c Gas that is escaping could be replaced from the supply.
What equipment must be used to pin point the source of a gas escape?
a A U tube manometer.
b An electronic gas detector.
c Diluted washing up liquid.
d Leak detector solution.
d Leak detector solution.
When testing a new installation with air prior to the installation of a gas supply, it is not necessary to allow 1 minute for stabilization:
a. True.
b. False.
b. False.
If, when carrying out a tightness test, the readings on each side of a U gauge are 16mbar and 20mbar, the pressure at which the test is being carried out is:
a 16mbar.
b 20mbar.
c 18mbar.
d 36mbar.
c 18mbar.