Module 10.1 Knowledge Questions Flashcards
Where upon a gas appliance will the gas installer find information regarding the correct burner pressure and input?
Answer…..
Data badge
Range rated appliances must incorporate what component within their design:
a A fan pressure sensor.
b A constant pressure governor.
c A air sensing device.
d A re-ignition device.
b A constant pressure governor.
A likely cause of excessive working pressure at a gas fire or cooker is:
a A partially blockage in the supply.
b An incorrectly adjusted meter governor.
c Inadequate pipe sizing.
d Damaged pipework
b An incorrectly adjusted meter governor.
What is the input to a gas water heater it the test dial of a U6 meter takes 1 minute to complete one full revolution (take CV as 39MJ/m3)?
a 650kW.
b 23.kW.
c 18.2kW.
d 2.32kW.
c 18.2kW.
What is the rated input to a water heater if the initial reading on an E6 meter is 6848.421 and after 2 minutes with the heater running on full, is 6848.511?
(take CV as 39MJ/m3)
a 17.25kW.
b 26.25kW.
c 28.25kW.
d 29.25kW.
d 29.25
To measure the operating pressure of a gas appliance, the appliance must be:
a Turned off.
b Turned on low rate.
c Turned on full rate.
d lt may be either on or of.
c Turned on full rate.