Module 16 Domestic Central Heating Flashcards
Where a compartment containing an OF boiler or circulator the air vents must not communicate with:
a) a private garage
b) a bedroom
c) a bed-sitting room where the input rating >14kW gross
d) bath and/or shower room
e) all of the above
e) all of the above
If an OF appliance in a bedroom located compartment what additional steps should be taken?
4 of them
1) Self closing door
2) Draught proof door
3) Door kept shut at all times – unless access to controls required
4) Compartment must not be used for storage etc
If a boiler or circulator is installed in an under stairs cupboard what two additional factors should be considered
1) Really should be RS
2) All internal surfaces 30 mins fire resistance
What is a circulator?
An appliance to provide hot water to a storage vessel
Gas fire hearth requirements – what are the minimum dimensions
M16/p20
A = 300mm
B = 150mm
At least 50mm above floor with a non-combust surface >12mm thick