LOT 201.35 Non-Class DGs Flashcards

1
Q
  • LOT 201.35 Non-Class DGs*
    • *

How are the Non-Class DGs started?

A
  • BOP / NTF / LTG:*
  • *Two 24 VDC Electric Starting Motors**
  • Rated for 10 Starts*
  • Flex:*
  • *One 24 VDC Electric Starting Motors**
  • TSC:*
  • *Air Driven Starting Motor (90 - 120 psig)**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  • LOT 201.35 Non-Class DGs*
    • *

Where are the Non-Class DGs physically located?

A
  • TSC DGs:*
  • *N of TB enclosed in Trump Wall**
  • BOP DGs:*
  • *31’ TB SE side**
  • Flex DGs:*
  • *MAB Roof**
  • Lighting DGs:*
  • *S Side between Units**
  • NTF DG:*
  • *W of NTF**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  • LOT 201.35 Non-Class DGs*
    • *

What prevents synchronizing a Non-Class DG onto a live bus?

A

Output CBs ELECTRICALLY interlocked to prevent being closed while normal bus feed is closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  • LOT 201.35 Non-Class DGs*
    • *

What trips the BOP / NTF / LTG DGs?

A

BOP / NTF / LTG:

  • *Engine Overspeed**
  • ≈ 115% (2073 rpm)*
  • *Lube Oil Pressure - Low**
  • (20 psig)*
  • *Cooling Water Temperature - High**
  • (210 ˚F)*
  • *Generator Overcurrent**
  • (2400 amps)*
  • *Generator Volts/Hertz NOT within Limits**
  • (2.2 V/Hz for greater than 15 seconds)*
  • N/A for Unit 2 BOP AND NTF*
  • *Engine Over crank [Lockout]**
  • (3 cycles)*

Ground Fault (NTF ONLY)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  • LOT 201.35 Non-Class DGs*
    • *

What trips the Flex DGs?

A
  • *Engine Overspeed**
  • (1980 rpm)*
  • *Lube Oil Pressure - Low**
  • (73 psig)*
  • *Cooling Water Temperature - High**
  • (215°F)*
  • *Coolant Level - Low**
  • (sensor in upper portion of radiator)*
  • *Engine Overcrank [Lockout]**
  • (3 cycles)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  • LOT 201.35 Non-Class DGs*
    • *

What loads does the Flex diesel supply?

A
  • Normal:*
  • *Flex RCS M/U Pumps**
  • *Flex S/G M/U Pumps**
  • *Flex SFP M/U Pumps**
  • Backup:*
  • *CVCS PDP**
  • *RCB Equipment Hatch Hoist**
  • B/U to TSC DG*
  • *480V ESF LC and MCC**

Supplies 480V LC DP1000

480 V / 1000 kW / 1800 RPM

  • Note:*
  • Within 8 hours following an Extended Loss of AC Power (ELAP) the FLEX Diesel Generator will be running providing power to support SG make-up, RCS make-up, SFP make-up, and other functions in support of STP’s FLEX strategies.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  • LOT 201.35 Non-Class DGs*
    • *

What trips the TSC DGs?

A
  • *Engine Overspeed**
  • ≈ 110% (1980 rpm)*
  • *Lube Oil Pressure - Low**
  • (30 psig)*
  • *Cooling Water Temperature - High**
  • (210 ˚F)*
  • *Loss of Excitation**
  • (≥ 2 sec)*
  • *Overcurrent**
  • (300 Amps)*

Phase Differential [Lockout]

  • *Engine Over crank [Lockout]**
  • (3 cycles)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  • LOT 201.35 Non-Class DGs*
    • *

What loads does the NTF DG supply?

A

Motor-Driven Fire Pump House

NTF Simulator

Feeds 480V 12N

BOP, NTF, and Security LTG DGs: 480 VAC / 700 KW / 1800 RPM

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  • LOT 201.35 Non-Class DGs*
    • *

What loads does the Security Lighting DG supply?

A

Security LTG

EAB UPS

Intake Structure LTG

Feeds 480V 12K3

BOP, NTF, and Security LTG DGs: 480 VAC / 700 KW / 1800 RPM

  • Note:*
  • Auto Starts on loss of voltage, comes up to speed and closes breaker in 15 seconds*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  • LOT 201.35 Non-Class DGs*
    • *

What loads does the BOP diesel supply?

A

Battery Chargers 125V/250V

IA Compressor 14

Turning gears for MFPs and Main Turbine

Bearing Oil Lift Pump

Air Side Seal Oil Pump

Feeds MCC 1G5

BOP, NTF, and Security LTG DGs: 480 VAC / 700 KW / 1800 RPM

  • Note:*
  • BOP DG Fuel Tank will last 60 mins
  • Auto Starts on loss of voltage, comes up to speed and closes breaker in 15 seconds
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  • LOT 201.35 Non-Class DGs*
    • *

When will the Non-Class DGs trip on overspeed?

A
  • BOP / NTF / LTG:*
  • *2073 RPM**
  • ≈115% of 1800 RPM*
  • TSC / Flex:*
  • *1980 RPM**
  • 110% of 1800 RPM*
  • Note:*
  • TSC DG also equiped with device to prevent overloading TSC DG during S/U. (Puts TDs on when loads can be started)*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  • LOT 201.35 Non-Class DGs*
    • *

What control room indications are their for the Non-Class DGs?

A
  • BOP / LTG / TSC:*
  • *CP003 (Trouble alarms)**
  • Flex / NTF:*
  • *None**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  • LOT 201.35 Non-Class DGs*
    • *

What loads does the TSC DG supply?

A

ICS Computer

CVCS PDP

FHB IVC LTG XFMRs

  • *RCB Equipment Hatch Hoist**
  • Flex DG provides B/U power*

Emergency XFMR cooling fans

Feeds 4.16 kV LC 1W1 → MCC 1G8

  1. 16 kV / 1200 kW / 1800 RPM
    * * *
  • Note:*
  • Auto Starts on loss of voltage, comes up to speed and closes breaker in 15 seconds*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q
  • LOT 201.35 Non-Class DGs*
    • *

What auto starts the Non-Class DGs?

A
  • BOP / NTF / LTG / TSC:*
  • *Bus Undervoltage**
  • 2 sec from UV to breaker shutting*
  • Auto start blocked if feeder breaker tripped on Overcurrent*
  • Flex:*
  • *No auto starts**

BOP / NTF / LTG / TSC:

  • Switch has 3 positions - Hand / OFF / AUTO
    • Auto allows UV start
    • OFF prevents start (TSC 5 min C/D)
    • Hand starts DG in manual (TSC requires pressing start button in addition to Hand)
  • Note:*
  • Pushing the Manual Auto to Bypass Pushbutton allows going from Hand to Auto w/o shutting down DG.*
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q
  • LOT 201.35 Non-Class DGs*
    • *

What are the Non-Class DG output breakers close permissives?

A
  • *Normal Supply Breaker Open**
  • *No overcurrent trip on supply breaker**
  • *No Lockout Relays energized**
  • *Mode Switch NOT in off**
  • *Remote Switch NOT in PTL (TSC ONLY)**
How well did you know this?
1
Not at all
2
3
4
5
Perfectly