Line D ? Valve Train Components Flashcards

1
Q

Define a Valve Train.

A

The combination of valves, controls, piping, and tubing of an appliance upstream from the manifold through which gas is supplied to the appliance and by which gas is controlled

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Where will you find the minimum standards for the design of fuel trains?

A

CSA B149.3, specifically annex B

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What three factors will determine the number and type of components in the valve train?

A

The appliance input, type/number of burners and gas pressure.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When gas and another fuel are used in a dual or combination burner, a manual isolation valve shall be provided upstream of the main gas valve train components but downstream of the pilot line connection.

True / False

A

True (B149.3 6.1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Where will you find the symbol legend for gas valve train components?

A

Figure B.1 in CSA B149.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What types of valve can be used for the manual shut-off of a valve train?

A

A valve approved for use with gas, and can be a Plug, ball or eccentric type B149.1 6.18.1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What percentage above or below regulator set pressure can we operate at, through the firing range of an appliance?

A

B149.3 4.4
10% boost (above set point)
10% droop (below set point)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

According to the B149.3, at what inlet pressure does a regulator need to be of a lockup style?

A

0.5 psig (3.5 kPa)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Define Overpressure Protection Device:

A

A device that under abnormal conditions will act to reduce, restrict, or shut off the supply of gas flowing into a system to prevent gas pressure in that system from exceeding the rated pressure of the system components.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the primary automatic valve used to start and stop the flow of gas?

A

Safety shut-off valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The downstream safety shutoff valve should be quick-opening, to provide smooth and reliable lighting of the burners.

True / False

A

False (B149.3 8.1.3 It should be slow-opening)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the maximum closing time required for a safety shut-off valve?

A

1 second

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is incorporated in a safety shut-off valve to make it a proof of closure switch?

A

An end switch that makes when the valve is in the closed position.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

The tightness of a SSOV closure is assumed to be good and does not need to be checked when servicing equipment.

True / False

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What components are included in a double block and bleed?

A

A double block and bleed has two SSOV and a vent valve installed between them

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Electrically, what type of automatic vent valve shall be used?

A

Normally open so that it closes when energized.

17
Q

On a 3” Valve train what size does that valve and vent line pipe need to be?

A

1 ¼”

18
Q

How shall the the safety vent valve (SVV) be wired in relation to the safety shut-off valves?

A

In parallel

19
Q

What is a valve proving system?

A

A system that proves the effective closure of safety shut-off valves by detecting leakage. It can consist of a programming unit, a measuring device, valves, and other functional assemblies.

20
Q

When is an input flow control valve required?

A

On installations where the firing rate is automatically changed

21
Q

Where is a test firing valve located?

A

Downstream of all safety shut-off valves on the valve train and as close to the burner as is practicable.

22
Q

What is the purpose of the test firing valve?

A
  • The purpose of a test firing valve is to give the Technician the ability to isolate the main burner and test/adjust the other valve train components while energized and live/gasified without firing the main burner.
  • The test firing valve is also used for manual control of the first main burner firing during commissioning. It gives the technician the opportunity to observe and listen to light-off under a more manual control.
23
Q

The test firing valve must not have stops in the OPEN and CLOSED positions?

True / False

A

False B149.3 6.2(d)