Line C 3-Phase Motor Starters & PID Loop Controls Flashcards

1
Q

What will the size of the wire be from the mag starter to motor if 230 volts is used?

A

6 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What will the size of the mag starter be if 460 volts is used?

A

NEMA 2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What size overloads are required for the motor starter if 460 volts is used?

A

31.25 Amps
25 amps
1.15 service equals 125% of 25 amps
less than 1.15= 115%
rule 28 -208?

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What will be the rated size of the disconnect time-delay fuses if 230 volts is used?

A

87.5 Amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

For a PID controller, what does the proportional do?

A

It produces an output value that is proportional to the current error value

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

For a PID controller, what does the derivative do?

A

It sums the error over time

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

For a PID controller, what does the proportional gain do?

A

It determines the ratio of output response to the error signal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

For a PID controller, what does the integral do?

A

It acts as a brake or dampener on the control effort

How well did you know this?
1
Not at all
2
3
4
5
Perfectly