Line D Permissives, Limits, & Interlocks Flashcards

1
Q

Modern burner controls do not need to be continuously powered.

A

FALSE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What initiates the burner cycle?

A

The Control Circuit switches being completed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

List some of the typical switches that could be found on the limit circuit of a boiler.

A

Manual switch, operating Aquastat, high limit Aquastat, low water cut-off, thermostat, DDC contacts, Pressuretrol, flow switch, aux-low water cut-off.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the purpose of an interlock?

A

To stop the burner from firing to prevent an appliance from damaging itself if a condition fails to be satisfied.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What must be done when a non-recycling interlock opens?

A

It must be reset manually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What feature shall be included on a low water cut-off that is an interlock for a water boiler that is located above the hot-water circulating system?

A

It must have a manual reset feature.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Define Permissive:

A

Conditions that need to be satisfied before you can start the equipment cycle.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Define Interlock:

A

Prevents an appliance from damaging itself if a condition fails to be satisfied.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

List the common run interlocks:

A

Combustion Air Proving Switch (CAPS), Mag Starter Aux Switch, Low gas Pressure Switch (LGPS), High Gas Pressure Switch (HGPS), Oil Temp Switch, Low Oil Pressure Switch, Low Atomizing Media Switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What type of interlock is required when combustion air is supplied by mechanical means?

A

A combustion air proving switch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the “normal” position of a combustion air proving switch?

A

Open (NO)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the purpose of the purge interlock:

A

To prove adequate air supply before the start of the pre-purge countdown timer and during the purge period.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the purpose of a low fire start interlock?

A

To prove combustion air damper and fuel valve are in low fire position before ignition.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How many air changes of the combustion zone and flue passages must take place during the pre-purge period prior to the ignition cycle?

A

4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When shall a proven low fire start be required?

A

On a variable input appliance that has an input in excess of 1,000,000 BTUH, unless otherwise approved.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

List 4 types of pre-ignition interlocks:

A

Start interlock, fuel valve switch, proof of closure switch, overtravel proof of closure switch

16
Q

Define proof of closure switch:

A

A factory sealed switch incorporated into a safety shut-off valve that includes at least one set of contacts, which close only after the valve port is closed and which open prior to the opening of the valve port.

17
Q

What type of switch is pictured below?

A

Over Travel Proof of Closure Switch