Install Flame Safeguard Flashcards

1
Q

What is the minimum operating ambient temperature for the control?

A

-40°C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the maximum operating ambient temperature for the control?

A

140°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the required minimum line voltage supply for the control?

A

85 Vac

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the maximum full load amps (FLA) allowed on terminal 4 for the RM7895?

A

9.8 amps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What is the maximum relative humidity the control is designed to operate?

A

85%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is the maximum continuous vibration the control can be subjected to?

A

0.5G

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Can the control’s wiring subbase be mounted in the horizontal position?

A

NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

At what amperage must the dedicated earth ground be capable of conducting the current to blow at?

A

15A

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

If a Data ControlBus Module is used what type wire should be used?

A

Twisted pair shielded cable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

If the interconnection daisy chain of more than two modules, i.e. Data ControlBud, Modbus, etc., connections are longer than 100 feet, what must be done?

A

A 13 Vdc full-wave rectified transformer needs to be installed separately to the daisy chain

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What size and type of wire should be used for a remote reset module?

A

22 AWG two-wire twisted pair

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

How should the signal ground be connected to modules installed in a daisy chain?

A

Connect the wire’s shield at both ends of the daisy chain

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What is the maximum length of wire for a reset module pushbutton?

A

1000 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

How many inches below the relay module are needed for the flame amplifier mounting?

A

2 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly