What is the minimum operating ambient temperature for the control?
-40°C
What is the maximum operating ambient temperature for the control?
140°F
What is the required minimum line voltage supply for the control?
85 Vac
What is the maximum full load amps (FLA) allowed on terminal 4 for the RM7895?
9.8 amps
What is the maximum relative humidity the control is designed to operate?
85%
What is the maximum continuous vibration the control can be subjected to?
0.5G
Can the control’s wiring subbase be mounted in the horizontal position?
NO
At what amperage must the dedicated earth ground be capable of conducting the current to blow at?
15A
If a Data ControlBus Module is used what type wire should be used?
Twisted pair shielded cable
If the interconnection daisy chain of more than two modules, i.e. Data ControlBud, Modbus, etc., connections are longer than 100 feet, what must be done?
A 13 Vdc full-wave rectified transformer needs to be installed separately to the daisy chain
What size and type of wire should be used for a remote reset module?
22 AWG two-wire twisted pair
How should the signal ground be connected to modules installed in a daisy chain?
Connect the wire’s shield at both ends of the daisy chain
What is the maximum length of wire for a reset module pushbutton?
1000 feet
How many inches below the relay module are needed for the flame amplifier mounting?
2 inches