Line B Hydronic Systems Flashcards

1
Q

What is the primary concern with ICI hydronic system design?

A

Protection of the equipment

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are two major concerns for the boiler in an ICI hydronic system installation?

A

Thermal shock and condensing combustion products

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the typical system design temperature difference for a non-condensing ICI boiler?

A

20°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the standard system design temperatures for a non-condensing ICI hydronic boiler?

A

180°F supply, 160°F return

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What type of boiler is best suited to handle the thermal shock?

A

Flex tube

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What minimum return water temperature must be maintained to avoid condensing of combustion products?

A

140°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

On an ICI hydronic heating system, what is the best location to install an air separator?

A

Immediately after the boiler supply outlet.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Why is it recommended to install the boiler outlet, air separator and expansion tank on the suction side of the system circulator pump?

A

To decrease air entry into the system piping and prevent imposing system head on the boiler supply.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Where is it recommended the system feed water be connected?

A

Into the air vent piping on the air separator

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the purpose of a hydraulic de-coupler?

A

To isolate the source pump(s) from the load pump(s)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly