Line A Combustion Analyzers Flashcards
What is the main reason for performing combustion analysis on gas fired equipment?
To ensure the equipment is operating in a safe and efficient manner.
How often should your combustion analyser be calibrated to ensure accurate test readings?
Once per year.
Where should the sampling probe take a sample from on a gas fired appliance?
Upstream of any draft control device or just downstream of a stack economizer.
What is the correct way to allow combustion analysis samples to be taken with plastic S636 systems?
Installing an access tee with a ½” tapped bushing as close as possible to the flue collar of the appliance where either a plastic or brass plug can be inserted.
What is a Peltier cooler used for in a combustion analyzer?
To drive out moisture from the sample
The gas cells in a combustion analyser are of what type?
Electrochemical
What can shorten the life span of the toxic sensors in a combustion analyser?
High gas concentrations or insufficient purging
What is the chemical formula for the Perfect combustion of Natural Gas?
1CO2 + 2H2O = 8N2
What is the chemical formula for the Perfect combustion of Propane?
3C02 + 4H2O = 20N2
What is added to the combustion process to produce Complete combustion?
Excess Air
What is the expected percentage range of O2 produced by a forced draft burner with CH4 as the fuel?
3% - 6%
What are four characteristics of Carbon Monoxide?
Toxic, colourless, odourless and tasteless
What can cause too much draft in a venting system?
High stack temperatures
What percentage gain in efficiency is achieved by lowering stack temperature by 45⁰F?
Less than 1%
Calculate the net stack temperature if the ambient temperature is 72⁰F and the stack temperature is 420⁰F? Is this temperature within typically expected values?
348⁰F, Yes (330 - 500⁰F)