Lesson 8: Aux. Circ, Water system Flashcards

1
Q
  1. What is the purpose of the Auxiliary Circulating System?
A

It cools the ACW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  1. What is the purpose of the heat exchanger?
A

Transfers heat from the ACW to the Aux. Circ. Water

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  1. Draw a one line diagram showing the flow of the auxiliary circulating system?
A

Cooling Tower - Aux Circ Pump - Heat Exchangers (YUBAS) - Return to Cooling Tower

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  1. What is the purpose of the air purging system?
A

It removes air from the system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. What voltage is the Aux. Circulating pump motor?
A

4160 Volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  1. What should be checked on the motor and pump before starting? After Starting?
A

Pre-Start:

Breaker racked in
Safe/Run in Run
Discharge Valve closed (air blocked)
Suction Valve open
Oil leaks
Oil Levels
Water Leaks and expansion joint condition
Motor air intakes clear
Bleed air out of pump
Verify instrument air is blocked to discharge valve,
if other pump is running note the discharge pressure.

Post Start:

Outlet Valve open
Heat/Vibration on motor and pump bearings.
Oil levels on motor/pump
Check for leaks and expansion joint		
Slinger Rings
Oil Levels						
Leaks, packing leak off.
Discharge pressure = 35psi
Verify instrument air is open for discharge valve,
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  1. What is the purpose of the amertap system?
A

It cleans the inside of the tubes in the Condenser and the YUBAs.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  1. Why should we be concerned about a high differential pressure across the screens on the amertap system?
A

A high DP indicates that the screens could be full of debris.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  1. How many balls does the amertap system hold? What size balls does it take?
A

YUBA – 200, 25 mm balls. Condenser – 700, 27 mm balls.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  1. Does the Aux. Circulating water flow through the tubes of the heat exchanger or around the tubes?
A

Aux. Circ. Water runs through the tubes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  1. What is the purpose of the anodes and grounding straps on the heat exchanger?
A

To protect against scale and corrosion build up.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  1. Describe putting the system in service.
A
  1. Breaker racked in
  2. Safe/run in run
  3. Suction valve open
  4. Discharge valve closed
  5. Instrument air blocked if its the first pump, or open to discharge valve if not
  6. Put the Discharge valve switch in auto
  7. Crack open inlet valve to YUBA heater
  8. Open vents on YUBA
  9. Aux circ pump checks
  10. Cooling tower level is raised to 82 inches
  11. Bleed off the air in the pump
  12. When you have good flow start the pump and bleed/vent the air out of the YUBA
  13. When YUBA has good flow open inlet and outlet valves fully open on YUBA
  14. Close YUBA vent
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q
  1. Why do we use inverted cooling flow?
A

Inverted flow provides a better transfer of heat.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly