Lesson 7: Transformers Flashcards

1
Q
  1. What is the function of a transformer?
A

To either step up or step-down voltage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q
  1. List the items that should be checked on a transformer.
A
Fans operating when put in manual
Oil Level
Oil Temp.
Oil Leaks
Nitrogen Pressure
Grounding Strap
Fins clear of debris
Hot spots/Arcing
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q
  1. List the buses associated with the following equipment:
    a) Precipitator-
    b) Cooling Tower-
    c) Ponds-
    d) Boiler/Steam Generator equipment-
    e) Lagoons East and west-
    f) Bag House-
A

a) R, S
b) F, G, M
c) T
d) D, E, H
e) F, G, M
f) J, K

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q
  1. Our station power consists of 3 main voltages. What are they?
A

6900 V
4160 V
480 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q
  1. List the voltages on the following buses
    a) A & B
    b) P & Q
    c) All others
A

a) 6900 V
b) 4160 V
c) 480 V

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q
  1. List the equipment serviced by “A” bus 6900v, “B” bus 6900v.
A
ID Fans
FD Fans
Soot Blower Air Compressors
Electric Fire Pump
480 Transformers
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q
  1. List the equipment serviced by “P” bus 4160v, “Q” bus 4160v.
A

Coal Mills
Circulating Water Pumps
Aux. Circulating Water Pumps

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q
  1. List all the 480v buses on Unit #1, #2 and #3.
A

Unit #1: D,E,H, F,G,M, J,K R,S T

Unit #2&3: D,E,H, F,G,M, J,K

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q
  1. What safety precautions should always be observed before racking out a breaker?
A

Equipment is NOT running
CRO is aware of the breaker being racked out
Hold Card matches the appropriate equipment
Arc Flash suit is on

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q
  1. List the items to be checked on all breakers.
A
Hot Spots
Fire/Smoke
Weird Smells
Unusual Noises
Arcing
Flag Indicators
Indicator Lights
Tags
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q
  1. Explain the Kirk Key operation (CT Circ. Pump). Where are the Kirk Keys located?
A

It’s an Interlock System that allows the isolation of equipment. Used in High Voltage Switch Gear and the TR sets.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q
  1. Explain how to manually close or open any size breaker.
A
Open:			
Verify equipment is
not running			               
Wear proper PPE				
Call CRO						   
Rack breaker out			           
Place hold cards
Close:
Wear proper PPE
Remove Hold cards
Call CRO
Rack breaker In
How well did you know this?
1
Not at all
2
3
4
5
Perfectly