Irrigation Flashcards
A double check assembly may be used in irrigation systems with ____ ____ of a ____ ____. If a double check assembly is installed below grade, a ____ must be installed on the inlet side of the unit.
no threat of a health hazard
Y-strainer
An RP back-flow device must be used if there are any ____ ____, if there is ____ ____ ____ water source, if there are chemicals added by ____, ____, or ____, or if there is an ____ system on site.
chemicals added
more than one
aspiration, injection, emission
OSSF
Piping and valves must meet separation distances from an ____ system.
OSSF
If a master valve is used, it must be installed downstream from the ____ device.
backflow
New irrigation systems may not use spray emission devices in landscapes less than ___ inches across in width or length.
48”
Above ground sprinklers may not be installed closer than ___ inches from any hardscape.
4”
Sprinklers may not directly spray on or over surfaces such as ____, ____ ____, ____, ____, ____, ____, et cetera.
concrete, building structures, walls, fences, sidewalks, streets
All irrigations systems must have a ____ or moisture ____ ____ ____ or sensor. Repairs that require replacing the controller require ____ ___ ____ if not already in place.
rain
shut off device
installing a sensor
All new irrigation systems require an ____ valve.
isolation
Minimum irrigation system depth is ___ inches and ___ inches if there are unavoidable roots, utilities, or other obstacles.
6”
2”
All electrical wiring in irrigation systems must be ____ ____ for ____ ____ and buried a minimum of ___.
UL approved for direct burial
6”
____ or ____ water usage such as ____ ____ or ____ ____ shall not be connected to an irrigation system.
Drinking or domestic
swimming pools
decorative fountains
A licensed ____ or ____ ____ shall be onsite when an irrigation system is installed.
irrigator or irrigation technician
Upon completion of an irrigation system, the irrigator must furnish a final ____, a ____ checklist, a ____ ____ on the _____, and an ____ ____.
final walkthrough
maintenance checklist
service sticker on the controller
as-built plan
When repairs are completed at the water meter or back-flow device, an ____ ____ must be installed if there is not already one present.
isolation valve