HW Test #3 Flashcards
the feeder conductor ampacity shall be less than that of the service-entrance conductors where the feeder conductors carry the total load supplied by service conductors with an ampacity of _______ or less
55 A
310.15(b)(6)
for other than dwelling occupancies, banks, or office buildings, each receptacle outlet shall be calculated at not less than _____ VA.
180
How many receptacle outlets are permitted on a 20 A, 120 V circuit in a commercial building?
13
for show-window lighting, a load of not less than 660 volt-amperes/ linear meter or ____ volt amperes/ linear foot shall be included for show window measured horizontally along its base
200
open conductors which are not service entrance cables shall not be installed (above grade) less than which of the following
10 feet below grade level
what is the feeder or service calculated load for a waste disposal (940 VA), dishwasher (1250 VA), a trash compactor (1100 VA), and a water heater (4500 VA)?
5843 VA
a load demand factor of 75 percent is permitted for _____ or more appliances fastened in place such as waste disposals, dishwashers, trash compactors, water heaters, etc
four or more
what is the feeder or service calculated load for a waster disposal (940 VA), dishwasher (1250 VA), and a water heater (4500 VA)?
6690 VA
open conductors shall be __________ on glass or porcelain knobs, racks, brackets, or stain insulators
supported
open conductors installed outside shall be separated from open conductors of other circuits or systems by not less than ____
4 in
225.14(c)
the minimum clearance for overhead feeder conductors not exceeding 600 V that pass over commercial areas subject to truck traffic is ______
18 feet
overhead feeder conductors shall have a minimum _____ vertical clearance over residential property and driveways, as well as those commercial areas not subject to truck traffic, where the voltage is limited to 300 volts to ground
12 feet
225
conductors are considered outside a buildings when they are buried under not less than
2 “
230.6
service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of ______ from windows that are designed to be opened, doors, porches, stairs, fire escapes, or similar locations
3 feet
service drops installed over roofs shall have a vertical clearance of ______ above the roof surface, unless a lesser distance is permitted by an exception
8 feet