Article 200 (1 page, 10 questions) Flashcards
Article 200 contains the requirements for ____
all of these:
-identification of terminals
-grounded conductors in premises wiring systems
-identification of grounded conductors
the continuity of a grounded conductor shall not depend on a connection to a _____
any of these:
-metallic enclosure
-raceway
-cable armor
200.2 (B)
an insulated grounded conductor of ______ or smaller shall be identified by a continuous white or gray outer finish, or by three continuous white stripes on other than green insulation along its entire length
6 AWG
200.6 (A)
grounded conductor larger than _____ can be identified by distinctive white or gray markings at their terminations
6 AWG
the white conductor within a cable can be used for the ______ conductor where permanently reidentified to indicate its use an ungrounded conductor at each location where the conductor is visible and accessible
ungrounded
200.7
the white conductor within a cable can be used for switch loops if the white conductor is permanently reidentified to indicate its use at all terminations where the conductor is visible and accessible
TRUE
200.7(C)(2)
the indentification of _____ to which a grounded is to be connected shall be substantially white in color
terminals
receptacles shall hvae the terminal intended for connection to the grounded conductor identified by a metal or metal coating that is substantially ______ in color
white OR gray
the screw shell of a luminaire or lampholder shall be connected to the
grounded conductor
no _________ shall be attached to any terminal or lead so as to reverse designated polarity
grounded conductor