article 210 (8 pages, 72 questions) Flashcards
the rating of a branch circuit shall be determined by the rating of the _____
ampacity of the largest device connected to the circuit
210.3
a three-phase, 4-wire, ______ power system used to supply power to nonlinear loads may necessitate that the power system design allow for the possibility of high harmonic current on the neutral conductor
wye-connected
210.4
each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all _______ conductors at the point where the branch circuit originates
ungrounded
210.4
multiwire branch circuits shall _____
supply only line-to-neutral loads
210.4(c)
the ungrounded and grounded conductors of each _______ shall be grouped by wire ties or similar means in at least one location within the panel board or other point of origination
multiwire branch circuit
210.4 (D)
where more than one nominal voltage system exists in a building, each _____ conductors of a branch circuit shall be identified by phase and system at all termination, connection, and splice points
ungrounded
210.5(C)
in dwelling units, the voltage between conductors that supply the terminals of _____ shall not exceed 120V, nominal
-luminaires
-cord-and-plug-connected loads of 1,440 VA of less
210.6(A)
where two or more branch circuits supply devices or equipment on the same yoke, a means to disconnect simultaneously all ungrounded conductors that supply those devices or equipment shall be provided ____
at the point where the branch circuit originates
210.7(B)
all 15A and 20A, 125V receptacles installed in bathrooms of ____ shall have ground-fault circuit-interrupter (GFCI) protection for personnel
-guest rooms in hotels/ motels
-dwelling units
-office buildings
210.8(A)(1)(B)(1)
GFCI protection shall be provided for all 15A and 20A, 125V receptacles installed in a dwelling unit _____
garaje
210.8(A)(2)
GFCI protection shall be provided for all 15A and 20A, 125V receptacles in dwelling unit accessory buildings that have a floor located at or below grade level not intended as ______ and limited to storage areas, work areas, or similar use.
-habitable rooms
-finished space
210.9(A)(2)
all 15A and 20A, 125V receptacles installed in crawl spaces at or below grade level of dwelling units shall have GFCI protection
TRUE
210.8(A)(3)
al 15A and 20A, 125V receptacles installed in ____ of dwelling units shall have GFCI protection,
unfinished attics
210.8(A4-5)
GFCI protection shall be provided for all 15A and 20A, 125V receptacles ________in dwelling unit kitchens
installed to serve the countertop surfaces
GFCI protection shall be provided for all 15A and 20A, 125V receptacles located within 6ft of a dwelling unit______
-laundry sink
-utility sink
-wet bar sink
210.8(A)(7)
all 15A and 20A, 125V receptacles installed in a dwelling unit boathouses shall have GFCI protection
true
210.8(A)(8)
all 15A and 20A, 125V receptacles _______ of a commercial occupancies shall have GFCI protection
-in bathrooms
-on rooftops
-in kitchens
210.8(B)(1-3)
in other than dwelling units, GFCI protection shall be provided for all outdoor 15A and 20A, 125V receptacles
TRUE
120.8(B)(4)
ground-fault circuit-interrupter protection shall be provided for outlets not exceeding 240V that supply boat hoists installed in dwelling unit locations
TRUE
210.8(C)
two or more _____ small-appliance branch circuits shall be provided to supply power for receptacles outlets in the dwelling unit kitchen, dining room, breakfast room, pantry, or similar dining areas
20A
210.11(C)(1)
there shall be a minimum of one _______ branch circuit for the laundry outlet(s) required by 210.52(F)
20A
210.11(C)(2)
an individual 20A branch circuit can supply a single dwelling unit bathroom for receptacle outlet(s) and other equipment within the same bathroom
TRUE
210.11(C)(excep)
all 15A, or 20A, 120V branch circuits that supply outlets in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be AFCI protected by a listed arc-fault circuit interrupter of the combination type
TRUE
210.12(B)
an arc-fault circuit interrupter can be located at the first outlet to provide protection for the remaining portion of the branch circuit if_________
the circuit conductors up to the arc-fault circuit interrupter are in a metal raceway or Type AC cable
210.12(B)(except)(1)
branch-circuit neutral conductors that supply a continuous load shall have an ampacity of not less that 125 percent of the continuous load
FALSE
210.19 (A)(1)(excp)(2)
the recommended maximum total voltage drop on branch-ciruit conductors is ______ percent
3
210.19(A)(1)(fpn)(4)
where a branch circuit supplies continuous loads, or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less the noncontinuous load plus 125 percent of the continuous laod
TRUE
a single receptacle installed on an individual branch circuit shall have an ampere rating not less than that of the branch circuit
TRUE
210.21(B)(1)