Article 225 (2pg, 20 q) Flashcards

1
Q

open individual conductors shall not be smaller than ______ AWG copper for spans up to 50ft in length and _______ AWG copper for a longer span, unless supported by a messenger wire

A

10, 8

225.6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

the point of attachment of overhead premises wiring to a building shall in no case be less than _____ above finished grade

A

10 feet

225.18(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

where a mast is used for overhead conductor support, it shall be of adequate strength or be supported by braces or guys to withstand safely the strain imposed by the overhead drop

A

True

225.17

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

head feeder conductors shall have a minimum _______ vertical clearance over residential property and driveways, as well as those commercial areas not subject to truck traffic, where the voltage is limited to 300 volts-to-ground

A

12 feet

225.18

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

the minimum clearance for overhead feeder conductors not exceeding 600V that pass over commercial areas subject to truck traffic is _________

A

18 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

overhead feeder conductors installed over roods shall have a vertical clearance of _____ above the roof surface, unless permitted by an exception

A

8 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

if a set of 120/240 V overhead feeder conductors terminates at a through-the-roof raceway or approved support, with less than 6ft of these conductors passing over the roof overhand, the minimum clearance above the roof for these conductors is ______

A

18 inches

225.19 A
Exception 3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

the requirement for maintaining a 3ft vertical clearance from the edge of the roof shall not apply to the final feeder conductor span where the conductors are attached to _______

A

the side of a building

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

overhead feeder conductors to a building shall have a vertical clearance of final spans above, or within _____ measured horizontally from the platforms, projections, or surfaces from which they might be reached

A

3 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

outside wiring shall not be installed beneath openings through which materials may be moved, and shall not be installed where they will obstruct entrance to these buildings’ openings

A

TRUE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

raceways on exterior surfaces of building or other structures shall be arranged to drain, and in _____ locations shall be raintight

A

Wet

225.22

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

vegetation such as trees shall not be used for support of ______

A

Conductor spans

225.26

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

a building or structure shall be supplied by a maximum of _____ feeder(s) or branch circuit(s), unless specifically permitted otherwise

A

One

225.30

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

disconnecting means for a building supplied by a feeder shall be installed at a(n) _______ location

A

Readily accessible

225.32

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

where documented safe switching procedures are established and maintained and monitored by ________ individuals, the disconnecting means for a building supplied by a feeder can be located elsewhere on the premises

A

Qualified

225.32
Exception 1

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

there shall be no more than _____ switches or circuit breakers to serve as the disconnecting means for a building supplied by a feeder

A

Six

225.33 A

17
Q

the two to six disconnects for a disconnecting means for a building supplied by a feeder shall be_______

A

Grouped

225.34 A

18
Q

in a multiple-occupancy building, each occupant shall have access to his or her own _______

A

Disconnecting means

225.35

19
Q

when the disconnecting means for a building supplied by a feeder is a power-operated switch or circuit breaker, it shall be able to be opened by hand in the event of a ________

A

Power failure

225.38 (A)

20
Q

the disconnecting means for a building supplied by a feeder shall plainly indicate whether it is in the _______ position

A

Open or closed

225.38(D)