Article 225 (2pg, 20 q) Flashcards
open individual conductors shall not be smaller than ______ AWG copper for spans up to 50ft in length and _______ AWG copper for a longer span, unless supported by a messenger wire
10, 8
225.6
the point of attachment of overhead premises wiring to a building shall in no case be less than _____ above finished grade
10 feet
225.18(1)
where a mast is used for overhead conductor support, it shall be of adequate strength or be supported by braces or guys to withstand safely the strain imposed by the overhead drop
True
225.17
head feeder conductors shall have a minimum _______ vertical clearance over residential property and driveways, as well as those commercial areas not subject to truck traffic, where the voltage is limited to 300 volts-to-ground
12 feet
225.18
the minimum clearance for overhead feeder conductors not exceeding 600V that pass over commercial areas subject to truck traffic is _________
18 feet
overhead feeder conductors installed over roods shall have a vertical clearance of _____ above the roof surface, unless permitted by an exception
8 feet
if a set of 120/240 V overhead feeder conductors terminates at a through-the-roof raceway or approved support, with less than 6ft of these conductors passing over the roof overhand, the minimum clearance above the roof for these conductors is ______
18 inches
225.19 A
Exception 3
the requirement for maintaining a 3ft vertical clearance from the edge of the roof shall not apply to the final feeder conductor span where the conductors are attached to _______
the side of a building
overhead feeder conductors to a building shall have a vertical clearance of final spans above, or within _____ measured horizontally from the platforms, projections, or surfaces from which they might be reached
3 feet
outside wiring shall not be installed beneath openings through which materials may be moved, and shall not be installed where they will obstruct entrance to these buildings’ openings
TRUE
raceways on exterior surfaces of building or other structures shall be arranged to drain, and in _____ locations shall be raintight
Wet
225.22
vegetation such as trees shall not be used for support of ______
Conductor spans
225.26
a building or structure shall be supplied by a maximum of _____ feeder(s) or branch circuit(s), unless specifically permitted otherwise
One
225.30
disconnecting means for a building supplied by a feeder shall be installed at a(n) _______ location
Readily accessible
225.32
where documented safe switching procedures are established and maintained and monitored by ________ individuals, the disconnecting means for a building supplied by a feeder can be located elsewhere on the premises
Qualified
225.32
Exception 1